Water closets in bathrooms or powder rooms required to be accessible shall comply with this section.
Search Results "Multifamily Dwelling (HUD 504)"
-
1134A.7 Water closets
-
1134A.7 Water closets
Water closets in bathrooms or powder rooms required to be accessible shall comply with this section. 1. Floor space and location. The minimum floor space provided at a water...
-
1134A.7, Item 1
1. Floor space and location. The minimum floor space provided at a water closet shall be 48 inches (1219 mm) in clear width. The clear floor space shall extend past the front edge of...
-
1134A.7, Item 2
2. Reinforced walls for grab bars. Where the water closet is not placed adjacent to a side wall capable of accommodating a grab bar, the bathroom shall have provisions for...
-
1134A.7, Item 3
3. Seat height. The minimum height of water closet seats shall be 15 inches (381 mm) above the floor.
-
1134A.7, Item 4
4. Water closet controls. Water closet controls shall be mounted no more than 44 inches (1118 mm) above the floor. The force required to activate controls shall be no greater than 5...
-
1134A.8 Lavatories, vanities, mirrors and towel fixtures
Bathrooms or powder rooms required to be accessible shall have at least one accessible lavatory. Where mirrors and towel fixtures are provided, at least one of each shall be...
-
1134A.8 Lavatories, vanities, mirrors and towel fixtures
Bathrooms or powder rooms required to be accessible shall have at least one accessible lavatory. Where mirrors and towel fixtures are provided, at least one of each shall be...
-
1134A.8, Item 1
1. Location. Vanities and lavatories shall be installed with the centerline of the fixture a minimum of 18 inches (457 mm) horizontally from an adjoining wall or fixture to allow for...
-
1134A.8, Item 2
2. Floor space. A clear maneuvering space at least 30 inches by 48 inches (762 mm by 1219 mm) shall be provided at lavatories and shall be centered on the lavatory.
-
1134A.8, Item 3
3. Cabinets. Cabinets under lavatories are acceptable provided the bathroom has space to allow a parallel approach by a person in a wheelchair and the lavatory cabinets are designed...
-
1134A.8, Item 4
4. Knee and toe space. Knee and toe space shall be provided by one of the following:
-
1134A.8, Item 4.1
4.1. The space beneath the lavatory shall be left clear and unobstructed;
-
1134A.8, Item 4.2
4.2. Any cabinet beneath the lavatory shall be removable without the use of specialized knowledge or specialized tools; or
-
1134A.8, Item 4.3
4.3. Doors to the cabinet beneath the lavatory shall be removable or openable to provide the required unobstructed knee and toe space. The knee and toe space shall be centered on...
-
1134A.8, Item 5
5. Finished floor. The finished floor beneath the lavatory shall be extended to the wall.
-
1134A.8, Item 6
6. Plumbing protection. Water supply and drain pipes under lavatories shall be insulated or otherwise covered to protect against contact. There shall be no sharp or abrasive surfaces...
-
1134A.8, Item 7
7. Lavatory faucet controls. Faucet controls and operation mechanisms shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist. The...
-
1134A.8, Item 8
8. Mirrors and towel fixtures. Where mirrors or towel fixtures are provided they shall be mounted with the bottom edge no higher than 40 inches (1016 mm) from the floor.
-
1135A.1 General
If clothes washing machines and clothes dryers are provided in covered multifamily dwelling units, one of each type of appliance shall be provided....
-
1135A.1 General
If clothes washing machines and clothes dryers are provided in covered multifamily dwelling units, one of each type of appliance shall be provided....
-
1150A.1 General
Covered multifamily dwellings in buildings without an elevator, located on sites with difficult terrain conditions or unusual characteristics, may employ the site impracticality tests in...
-
1150A.1 General
Covered multifamily dwellings in buildings without an elevator, located on sites with difficult terrain conditions or unusual characteristics, may employ the site impracticality tests in...
-
TEST NO. 1 – INDIVIDUAL BUILDING TEST
It is not required by this code to provide an accessible route when the terrain of the site is such that both of the following apply: 1. The slopes of the undisturbed site...