Clearance around a water closet shall be 60 inches (1524 mm) minimum measured perpendicular from the side wall and 56 inches (1422 mm) minimum measured perpendicular from the rear wall....
Search Results "Side Transfer Surface"
-
11B-604.3.1 Size
-
11B-604.3.1 Size
Clearance around a water closet shall be 60 inches (1524 mm) minimum measured perpendicular from the side wall and 56 inches (1422 mm) minimum measured perpendicular from the rear wall....
-
1023.9 Stairway identification signs
braille floor identification signs that comply with Chapter 11A, Section 1143A or Chapter 11B shall be located at the landing of each floor level, placed adjacent to the door on the latch side...
-
1023.9 Stairway identification signs
braille floor identification signs that comply with Chapter 11A, Section 1143A or Chapter 11B shall be located at the landing of each floor level, placed adjacent to the door on the latch side...
-
§27.5 Federal financial assistance
available assistance in the form of: (a) Funds; (b) Services of Federal personnel; or (c) Real or personal property or any interest in, or use of such property, including: (1) Transfers...
- AquaTrek2 ADA Step System
-
608.2.2.1 Clearance
EXCEPTION: A lavatory complying with 606 shall be permitted on one 30 inch (760 mm) wide minimum side of the clearance provided that it is not on the side of the clearance adjacent to the...
-
F231.4.1 Cubicles and Counters
At least 5 percent, but no fewer than one, of cubicles shall comply with 902 on both the visitor and detainee sides....
-
806.2.3 Sleeping Areas
At least one sleeping area shall provide a clear floor space complying with 305 on both sides of a bed....
-
608.2.2.1 Clearance
EXCEPTION: A lavatory complying with 606 shall be permitted on one 30 inch (760 mm) wide minimum side of the clearance provided that it is not on the side of the clearance adjacent to the...
-
806.2.3 Sleeping Areas
At least one sleeping area shall provide a clear floor space complying with 305 on both sides of a bed....
-
231.4.1 Cubicles and Counters
At least 5 percent, but no fewer than one, of cubicles shall comply with 902 on both the visitor and detainee sides....
-
11B-705.1.2.5 Blended transitions
Editor's Note: From DSA's "Summary of New and Amended 2025 California Building Code (CBC) Regulations for Accessibility in the Triennial Code Cycle: "Requirements for detectable warning surfaces...
-
Permitted Protrusions in Wheelchair Spaces: ADA Standard Section 1002.4.4.3
protrude a distance of 6 inches (150 mm) maximum along the front of the wheelchair space, where located 9 inches (230 mm) minimum and 27 inches (685 mm) maximum above the floor or ground surface...
-
11B-1002.4.4.3 Permitted protrusions in wheelchair spaces
protrude a distance of 6 inches (152 mm) maximum along the front of the wheelchair space, where located 9 inches (229 mm) minimum and 27 inches (686 mm) maximum above the floor or ground surface...
-
11B-1002.4.4.3 Permitted protrusions in wheelchair spaces
protrude a distance of 6 inches (152 mm) maximum along the front of the wheelchair space, where located 9 inches (229 mm) minimum and 27 inches (686 mm) maximum above the floor or ground surface...
-
Ramp
A walking surface that has a running slope steeper than 1:20....
-
502.3.4 Location
Access aisles shall be permitted to be placed on either side of the parking space except for angled van parking spaces which shall have access aisles located on the passenger side of the...
-
A4.16.5 Flush Controls
Flush valves and related plumbing can be located behind walls or to the side of the toilet, or a toilet seat lid can be provided if plumbing fittings are directly behind the toilet seat....
-
A4.16.5 FLUSH CONTROLS
Flush valves and related plumbing can be located behind walls or to the side of the toilet, or a toilet seat lid can be provided if plumbing fittings are directly behind the toilet seat....
-
Angled Van Spaces
However, where van spaces are angled, an access aisle is required for each space on the passenger side (§502.3.4)....
-
502.3.4 Location
Access aisles shall be permitted to be placed on either side of the parking space except for angled van parking spaces which shall have access aisles located on the passenger side of the...
-
11B-602.3 Operable parts
The flow of water shall be activated by a manually operated system that is front mounted or side mounted and located within 6 inches (152 mm) of the front edge of the fountain or an automatic...
-
11B-604.9.5 Flush controls
Flush controls shall be located on the open side of the water closet except in ambulatory accessible compartments complying with Section 11B-604.8.2....