(a) When patient bedrooms are being added or altered as part of a planned renovation of an entire wing, a department, or other discrete area of an existing medical facility, a percentage...
Search Results "Medical Inquiry"
Commonly Searched Documents
-
6.1(4)(a)
-
M303.1 General
Diagnostic equipment used by patients seated in a wheelchair shall comply with M303.
-
M303.2.2 Width
Wheelchair spaces shall be 36 inches (915 mm) wide minimum. EXCEPTION: Wheelchair spaces located on raised platforms shall be permitted to be 32 inches (815 mm) wide minimum to a...
-
M303.3.1 Vertical
Changes in level of ¼ inch (6.4 mm) high maximum shall be permitted to be vertical.
-
M303.3.2 Beveled
Changes in level between ¼ inch (6.4 mm) high and ½ inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
-
M303.4 Components
Where components of diagnostic equipment are used to examine specific body parts, the components shall be capable of examining the body parts of a patient seated in a wheelchair....
-
M303.2.4 Equipment Clearances
Where wheelchair spaces are entered from the rear and includes space beneath components, wheelchair spaces shall include knee and toe clearances complying with M303.2.4.1 for breast...
-
M303.3.2 Beveled (Section-by-Section Analysis)
The MDE NPRM proposed that for equipment with a change in level at the entry to the wheelchair space, level changes greater than ¼ inch but not greater than ½ inch would be required...
-
M303.2.2 Width (Section-by-Section Analysis)
The MDE NPRM proposed to require that diagnostic equipment used by patients seated in a wheelchair provide a wheelchair space that was at least 36 inches wide. There were no public...
-
M303.3.1 Vertical (Section-by-Section Analysis)
The MDE NPRM proposed that for equipment with a change in level at the entry to the wheelchair space, level changes of up to ¼ inch high are permitted to be vertical. This provision...
-
M303.4 Components (Section-by-Section Analysis)
The MDE NPRM proposed to require diagnostic equipment used by patients seated in a wheelchair which has components that are used to examine specific body parts, be capable of...
-
M303.1 General (Section-by-Section Analysis)
This is an introductory section.
-
Base Support [No specific provision—affects M303.2.4]
Base Support [No specific provision—affects M303.2.4] Recommendation: The final proposal on the base support is for 1½ inch high maximum base support with additional sloping...
-
Knee & Toe Space [M303.2.4]
Knee & Toe Space [M303.2.4] Recommendation: The final subcommittee’s recommendations increased the overall knee and toe space to a minimum of 28 inches, from the initially...
-
Communication Barriers
Poor communication between a provider and a person with a disability inhibits accurate diagnosis and treatment. (The limited time that doctors spend during visits is also a barrier.)...
-
6.1(2)
(2) Hospitals and rehabilitation facilities that specialize in treating conditions that affect mobility, or units within either that specialize in treating conditions that affect...
-
M303.2.4 Knee and Toe Clearance
Wheelchair spaces shall include knee and toe clearance complying with M303.2.4. The depth of the wheelchair space shall include knee and toe clearance of 17 inches (430 mm) minimum...
-
M303.2.4.1 Toe Clearance
Toe clearance shall be provided at a height of 9 inches (230 mm) above the floor to a depth of 6 inches (150 mm) maximum.
-
M303.4 Components
Where components of diagnostic equipment are used to examine specific body parts, the components shall be capable of examining the body parts of a patient seated in a wheelchair....
-
M303.3.1 Vertical
Changes in level of ¼ inch (6.4 mm) high maximum shall be permitted to be vertical.
-
M303.3.2 Beveled
Changes in level between ¼ inch (6.4 mm) high and ½ inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
-
M303.2.4.2 Knee Clearance
Knee clearance shall be provided at a depth of 11 inches (280 mm) minimum and 25 inches (635 mm) maximum at 9 inches (230 mm) above the floor and at a depth of 8 inches (205 mm)...
-
M303.1 General
Diagnostic equipment used by patients seated in a wheelchair shall comply with M303.
-
United States of America v. Genesis Healthcare System - Settlement Agreement
SETTLEMENT AGREEMENT BETWEEN THE UNITED STATES OF AMERICA AND GENESIS HEALTHCARE SYSTEM UNDER THE AMERICANS WITH DISABILITIES ACT Press Release