In the MDE NPRM the Access Board proposed to place the requirements for head and back support for diagnostic equipment used by patients in the supine, prone, or side-lying position...
Search Results "Table"
Commonly Searched Documents
-
M301.3.3 Head and Back Support (Section-by-Section Analysis)
-
Transfer Supports Location and Configuration M301.3 and M302.3
Transfer Supports Location and Configuration M301.3 and M302.3 Location of the transfer supports shall be a minimum of 6 inches to a maximum of 19 inches from the top of the...
-
5.3.2 Transfer Sides for Equipment Used by Patients in a Supine, Prone, or Side-Lying Position
5.3.2 Transfer Sides for Equipment Used by Patients in a Supine, Prone, or Side-Lying Position.
-
Gripping Surface Cross Section and Clearances M301, M302, and M305.2
Gripping Surface Cross Section and Clearances M301, M302, and M305.2 Gripping surface for transfer supports shall be free of sharp or abrasive elements and shall have rounded...
-
M301.3.1 Transfer Supports
Transfer supports shall be provided for use with the transfer sides required by M301.2.3 and shall comply with M305.2.
-
M301.3 Supports
Transfer supports, stirrups, and reclining surfaces shall comply with M301.3.
-
M301.3.3 Head and Back Support
Where the diagnostic equipment is used in a reclined position, head and back support shall be provided. Where the incline of the back support can be modified while in use, head and...
- Mockett TLKNB27 Original Kyros Leg 5" Base
-
6.13 Outdoor Constructed Features
Where provided on circulation paths or beach access routes at beaches, outdoor constructed features such as picnic tables, grills or water hydrants, shall comply with technical provisions...
-
5.4.1 Transfer Support Location for M301 and M302
Figure 5.4.1 Location and Length of Transfer Supports (SOURCE: Midmark Corporation) A: Table seat depth, 17 inches minimum B: Transfer support length, 15 inches minimum C: Distance...
-
5.1.1 Transfer Surface Height Adjustability Recommendation for M301 and M302
Adjustable height MDE, such as exam tables, imaging tables and chairs, will make it possible to position the transfer surface near the height of the seat of the mobility device....
-
M301.2.3.1 End Transfer Surface
End transfer surfaces shall be 28 inches (710 mm) wide minimum and 17 inches (430 mm) long minimum. EXCEPTION: Transfer surfaces for imaging equipment with bores shall be...
-
M301.2.3.2 Side Transfer Surface
Side transfer surfaces shall be 28 inches (710 mm) wide minimum and 28 inches (710 mm) long minimum. EXCEPTION: Transfer surfaces for imaging equipment with bores shall be...
-
M301.2.4 Unobstructed Transfer
Each transfer surface shall provide two unobstructed sides for patient transfer. EXCEPTIONS: 1. Obstructions no more than 3 inches (75 mm) deep shall be permitted to extend beyond...
-
M301.4 Lift Compatibility
Diagnostic equipment shall be usable with portable patient lifts and, when in use with such lifts, shall comply with M301.4.1 or M301.4.2. EXCEPTION: Where fixed overhead patient...
-
M301.2.4 Unobstructed Transfer (Section-by-Section Analysis)
In the MDE NPRM the Access Board proposed that each transfer side provide unobstructed access to the transfer surface, with an exception to permit temporary obstructions as long as...
-
M301.4 Lift Compatibility
Diagnostic equipment shall be usable with a patient lift and shall comply with M301.4.1 or M301.4.2.
-
M301.2.3 Transfer Sides
The transfer surface shall be located to provide options to transfer from a mobility device onto one short side (depth) and one long side (width) of the surface. Each transfer side...
-
(3) Adjustability: Transfer Surface Intermediate Heights
Adjustable height MDE, such as exam tables, imaging tables and chairs, will make it possible to position the transfer surface near the height of the seat of the mobility device....
-
M305.2.1 Location (Section-by-Section Analysis)
The Committee noted that: because of the size, diversity, and use of diagnostic imaging tables, this support will carry out different functions on different tables… This two-part...
- Kompan, Inc. ELE400101 - Ministudio Sand Play Structure
-
4.1.3 Wheelchair Seating Space
Clear floor or ground space that is at least 30 inches by 48 inches shall be provided at each seating space that is required to be accessible and positioned for a forward approach to the table...
-
Camp Living Area
The area in a camping unit that contains constructed features, such as picnic tables, grills, fire rings, utilities, and other related elements, and may be located adjacent to or near a...
-
11B-226.4 Baby diaper changing station
Baby diaper changing stations shall comply with Sections 11B-309 and 11B-902. Baby diaper changing stations when deployed shall not obstruct the required width of an accessible route...