The length of transfer supports shall comply with M305.2.2.1 or M305.2.2.2.
Search Results "Braille Position"
-
M305.2.2 Length
-
M305.3.1.1 Horizontal Position
The length of gripping surfaces on horizontal standing supports shall be 4 inches (100 mm) minimum except for diagnostic equipment containing a wheelchair space which shall comply...
-
M305.3.2.1 Horizontal Position
The height of the top of the gripping surface on horizontal standing supports shall be 34 inches (865 mm) minimum and 38 inches (965 mm) maximum above the standing surface.
-
11B-220.1.3 Three or more automatic teller machines or fare machines
Where three or more automatic teller machines or fare machines are provided at a location, at least 50 percent shall comply with Sections 11B-707.2 through 11B-707.8 and the rest...
-
11B-220.1.2 Two automatic teller machines or fare machines
Where two automatic teller machines or fare machines are provided at a location, one shall comply with Sections 11B-707.2 through 11B-707.8 and one shall comply with Sections...
-
11B-220.1.2 Two automatic teller machines or fare machines
Where two automatic teller machines or fare machines are provided at a location, one shall comply with Sections 11B-707.2 through 11B-707.8 and one shall comply with Sections...
-
11B-220.1.3 Three or more automatic teller machines or fare machines
Where three or more automatic teller machines or fare machines are provided at a location, at least 50 percent shall comply with Sections 11B-707.2 through 11B-707.8 and the rest...
-
5.5.1 Armrest Provision for M302
5.5.1 Armrest Provision for M302 Description: Diagnostic equipment used by patients in a seated position such as exam chairs typically have armrests....
-
Armrests (M302.3.2)
M302.3.2 would require armrests to be provided on diagnostic equipment used by patients in a seated position....
- Seton ADA Braille Sign - Emergency Exit Only 89424
-
a. Problem: Images Without Text Equivalents
Two commonly used technologies are screen readers and refreshable Braille displays....
- 703.4.1 Raised Letter and Braille Signage Height
-
M305.2.8 Fittings
Transfer supports shall not rotate within their fittings when in place for transfer.
-
M305.2.7 Clearance
Clearance between the transfer support gripping surface and adjacent surfaces or obstructions shall be 1 ½ inches (38 mm) minimum.
-
M305.2.7 Clearance (Section-by-Section Analysis)
In the MDE NPRM, the Access Board did not provide any specific requirements for clearances around the transfer support. However, in the preamble to the MDE NPRM the Access Board...
-
M305.2.3 Fittings
Transfer supports shall not rotate within their fittings.
-
M302.2.2 Sunset
The low transfer position height, Item A of M302.2.1, shall cease to have effect on [Insert date 5 years after date of publication in the Federal Register]. [sic]...
-
5.2.1.1 Transfer Surface Width Recommendations for M301
Transfer Surface Width Recommendations for M301 The Committee recommends a transfer surface of 28 inches minimum width for equipment used by patients in a supine, side-lying, or prone position...
- Innerface ARQ Interior Sign Frame System
- Innerface Clearview Interior Signage
-
M305.3.1.3 Vertical Position
The length of the gripping surface on vertical standing supports shall be 18 inches (455 mm) minimum.
-
M305.3.2.2 Vertical Position
The height of the lowest end of the gripping surface on vertical standing supports shall be 34 inches (865 mm) minimum and 37 inches (940 mm) maximum above the standing surface.
-
M305.3.2 Vertical Position
Where the support is vertical, it shall be 18 inches (455 mm) minimum in length and the bottom end of the support shall be 34 inches (865 mm) high minimum and 37 inches (940 mm) high...
-
M305.2.1 Location
Transfer supports shall comply with M305.2.1.1 or M305.2.1.2 and shall be located 1 ½ inches (38 mm) maximum measured horizontally from the plane defined by the nearest edge of the...