Signal Level: ADA Standard Section 407.4.8.2.2
Section 407.4.8.2.2: covers the current ADA Standards for the signal level of audible elevator car indicators.
-
11B-407.4.8.2.2 Signal level
The verbal annunciator shall be 10 dB minimum above ambient, but shall not exceed 80 dB, measured at the annunciator....
-
11B-407.4.8.2.2 Signal level
The verbal annunciator shall be 10 dB minimum above ambient, but shall not exceed 80 dB, measured at the annunciator....
-
11B-609.4 Position of grab bars
Grab bars shall be installed in a horizontal position, 33 inches (838 mm) minimum and 36 inches (914 mm) maximum above the finish floor measured to the top of the gripping surface, except...
-
11B-609.4 Position of grab bars
Grab bars shall be installed in a horizontal position, 33 inches (838 mm) minimum and 36 inches (914 mm) maximum above the finish floor measured to the top of the gripping surface, except...
-
2 - Specifications
The 3 - part format has places to include all requirements related to tolerances and measurement protocols....
-
1015.3 Height
Required guards shall not be less than 42 inches (1067 mm) high, measured vertically as follows: From the adjacent walking surfaces....
-
1015.3 Height
Required guards shall not be less than 42 inches (1067 mm) high, measured vertically as follows: From the adjacent walking surfaces....
-
Seats: ADA Standard Section 604.4
Section 604.4 covers the current ADA Standards for the water closet seats.
-
Height: ADA Standard Section 1009.4.2
The height of the transfer wall shall be 16 inches (405 mm) minimum and 19 inches (485 mm) maximum measured from the deck....
-
11B-1009.4.2 Height
The height of the transfer wall shall be 16 inches (406 mm) minimum and 19 inches (483 mm) maximum measured from the deck....
-
11B-1009.4.2 Height
The height of the transfer wall shall be 16 inches (406 mm) minimum and 19 inches (483 mm) maximum measured from the deck....
-
11B-608.2.2 Standard roll-in type shower compartments
Standard roll-in type shower compartments shall be 30 inches (762 mm) wide minimum by 60 inches (1524 mm) deep minimum clear inside dimensions measured at center points of opposing sides...
-
11B-608.2.2 Standard roll-in type shower compartments
Standard roll-in type shower compartments shall be 30 inches (762 mm) wide minimum by 60 inches (1524 mm) deep minimum clear inside dimensions measured at center points of opposing sides...
-
11B-604.4 Seats
The seat height of a water closet above the finish floor shall be 17 inches (432 mm) minimum and 19 inches (483 mm) maximum measured to the top of the seat....
-
11B-604.4 Seats
The seat height of a water closet above the finish floor shall be 17 inches (432 mm) minimum and 19 inches (483 mm) maximum measured to the top of the seat....
-
Transfer Height: ADA Standard Section 1002.6.2
The height of transfer device seats shall be 14 inches (355 mm) minimum and 24 inches (610 mm) maximum measured from the load and unload surface....
-
11B-1002.6.2 Transfer height
The height of transfer device seats shall be 14 inches (356 mm) minimum and 24 inches (610 mm) maximum measured from the load and unload surface....
-
11B-809.10.7.4 Seat height
Water closet seats shall be 15 inches (381 mm) minimum and 19 inches (483 mm) maximum measured to the top of the seat above the finish floor....
-
11B-809.10.7.4 Seat height
Water closet seats shall be 15 inches (381 mm) minimum and 19 inches (483 mm) maximum measured to the top of the seat above the finish floor....
-
11B-1002.6.2 Transfer height
The height of transfer device seats shall be 14 inches (356 mm) minimum and 24 inches (610 mm) maximum measured from the load and unload surface....
-
11B-812.8.7 Location
Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign....
-
11B-812.8.7 Location
Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign....