11B-215 FIRE ALARM SYSTEMS AND CARBON MONOXIDE ALARM SYSTEMS

11B-215.1 General.

Where fire alarm systems and carbon monoxide alarm systems provide audible alarm coverage, alarms shall comply with Section 11B-215.

Exception:  In existing facilities, visible alarms for fire alarm systems shall not be required except where an existing fire alarm system is upgraded or replaced, or a new fire alarm system is installed. 

[2010 ADAS] Advisory 215.1 General.  Unlike audible alarms, visible alarms must be located within the space they serve so that the signal is visible. Facility alarm systems (other than fire alarm systems) such as those used for tornado warnings and other emergencies are not required to comply with the technical criteria for alarms in Section 702. Every effort should be made to ensure that such alarms can be differentiated in their signal from fire alarms systems and that people who need to be notified of emergencies are adequately safeguarded. Consult local fire departments and prepare evacuation plans taking into consideration the needs of every building occupant, including people with disabilities.

11B-215.2 Public and common use areas.

Alarms in public use areas and common use areas shall comply with Chapter 9, Section 907.5.2.3.1

[2010 ADAS] 215.2 Public and Common Use Areas.  Alarms in public use areas and common use areas shall comply with 702.

11B-215.3 Employee work areas.

Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.2 can be integrated into the alarm system. 

[2010 ADAS] 215.3 Employee Work Areas.  Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with 702 can be integrated into the alarm system.

11B-215.4 Transient lodging.

Guest rooms required to comply with Section 11B-224.4 shall provide fire alarms complying with Chapter 9, Section 907.5.2.3.3, and carbon monoxide alarms, where provided, complying with Chapter 4.

[2010 ADAS] 215.4 Transient Lodging.  Guest rooms required to comply with 224.4 shall provide alarms complying with 702.

11B-215.5 Residential facilities.

Where provided in residential dwelling units required to comply with Section 11B-809.5, fire alarms shall comply with Chapter 9, Section 907.5.2.3.4 and carbon monoxide alarms shall comply with Chapter 4

[2010 ADAS] 215.5 Residential Facilities.  Where provided in residential dwelling units required to comply with 809.5, alarms shall comply with 702.

ETA Editor's Note

The ADA requirements included at Sections 11B-215.2 through 11B-215.5 are provided for information only. 2010 ADAS Section 702 refers to NFPA 72 for the scoping of visible alarms, while CBC Section 907.5.2.3 contains specific scoping.

[MORE INFO...]