Clear space complying with Section 11B-305.2 shall be provided as required for specific equipment....
Search Results "Clear Width"
-
11B-805.4.2 Equipment
-
Side Reach [4.2.6]
High and low reaches are based on a depth of reach no greater than 10 inches measured from the available clear floor space....
- American Standard Acrylic Shroud for American Standard Selectronic Faucets
-
Table 2: Summary of Department of Transportation Survey
0.49% +0.5% 7 Curb ramp, flare slope 0 5% 0.57% +0.5% 8 Curb ramp gutter counterslope 0 5% 0.58% +0.5% 9 Widths...
-
2. Accessible lavatory with knee and toe space
Accessible lavatory with knee and toe space below, faucet controls usable with a loosely closed fist, clear floor space for front approach, and lowered mirror....
-
III. CONCLUSION
For the foregoing reasons, neither Section 904.4.1 nor its exception requires clear counter space at sales and service counters subject to the ADA’s requirements....
-
Toilet Compartments
The clear floor space required for a baby changing table by TAS 902.2 may overlap the water closet clearance based on TAS 604.3.2 since baby changing tables are considered convenience “fixtures...
-
4.35.4 Bench
Clear floor space shall be provided alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench....
-
11B-604.3.2 Overlap
clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear...
-
11B-604.8.1.1 Size
Wheelchair accessible compartments shall be 60 inches (1524 mm) wide minimum measured perpendicular to the side wall, and 56 inches (1422 mm) deep minimum for wall hung water closets...
-
11B-604.8.1.1 Size
11B-604.8.1.1 Size. Wheelchair accessible compartments shall be 60 inches (1524 mm) wide minimum measured perpendicular to the side wall, and 56 inches (1422 mm) deep minimum for...
-
Polling places that cannot be remediated with temporary measures:
Building Entrance & Voting Area: The door at the designated accessible entrance does not provide at least 32 inches clear passage width when the door is open 90 degrees (1991 ADA Stds...
-
11B-604.3.2 Overlap
clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear...
-
11B-604.3.2 Overlap
clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear...
-
Water Closet Clearance
To allow greater transfer options, including side transfers, the 2010 Standards prohibit lavatories from overlapping the clear floor space at water closets, except in covered residential...
-
405.7.2 Width
The landing clear width shall be at least as wide as the widest ramp run leading to the landing....
-
405.7.2 Width
The landing clear width shall be at least as wide as the widest ramp run leading to the landing....
-
In a doctor’s office or clinic with multiple exam rooms, must every examination room have an accessible exam table and sufficient clear floor space next to the exam table?
Q In a doctor’s office or clinic with multiple exam rooms, must every examination room have an accessible exam table and sufficient clear floor space next to the exam table?...
-
Stair widths
There seem to be sections in CBC Chapter 10 that contradict each other regarding stair widths....
-
§ 38.127(c)
conditioning controls, lighting controls, call buttons, electrical outlets, etc.) shall be mounted no more than 48 inches, and no less than 15 inches, above the floor and shall have a clear...
-
Attachment J
with Fig. 28; and a flush control mounted on the “open” side of the toilet’s clear floor space. ...
-
29.1 Q. Is it acceptable to design a bathroom with an in-swinging 2'10 door which can be retrofitted to swing out in order to provide the necessary clear floor space in the bathroom?
Thus, for a bathroom, there must be sufficient maneuvering space and clear floor space so that a person using a wheelchair or other mobility aid can enter and close the door, use the fixtures...
-
ETA Questions: Interpretation of the "Changes in Level Are Not Permitted" Requirements
There are a number of places in the 2010 ADA Standards where the phrase "Changes in level are not permitted" occurs. However, the interpretation of this phrase is not clearly...