Two-way communication systems shall provide communication between each required location and a central control point location approved by the fire department. Where the central...
Search Results "Accessible Means of Egress"
-
1009.8.1 System requirements
-
1009.8.1.1 Visible communication method
[DSA-AC and HCD 1-AC] A button complying with Section 1138A.4 or Sections 11B-205 and 11B-309 _|Operable Parts|_ in the area of refuge shall activate both a light in the area of...
-
1009.8.2 Directions
Directions for the use of the two-way communication system, instructions for summoning assistance via the two-way communication system and written identification of the location...
-
1009.9 Signage
Signage indicating special accessibility provisions shall be provided as shown: 1....
-
1009.10 Directional signage
Direction signage complying with Chapter 11B, Section 11B-703.5 _|Signs; Visual Characters|_ indicating the location of the other means of egress and which of those are accessible means...
-
1009.12 Alarms/emergency warning systems/accessibility
If emergency warning systems are required, they shall activate a means of warning the hearing impaired....
-
Use of the International Symbol of Accessibility and Other Signs
On the door to an accessible area of refuge inside multistory buildings. At an accessible means of egress out of a building....
-
SECTION 1009 ACCESSIBLE MEANS OF EGRESS
-
1009.1 Accessible means of egress required
Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress....
-
1009.2 Continuity and components
Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: Accessible routes complying with Chapter...
-
1009.2.1 Elevators required
stories above the level of exit discharge, not less than one required accessible means of egress shall include an elevator complying with Section 1009.4....
-
1009.3 Stairways
In order to be considered part of an accessible means of egress, a stairway between stories shall comply with Sections 1009.3.1 through 1009.3.3....
-
1009.4 Elevators
In order to be considered part of an accessible means of egress, an elevator shall comply with Sections 1009.4.1 and 1009.4.2....
-
1009.4.2 Area of refuge
Areas of refuge are not required for elevators accessed from a refuge area in conjunction with a horizontal exit....
-
1009.5 Platform lifts
Platform lifts shall be permitted to serve as part of an accessible means of egress where allowed as part of a required accessible route in Chapter 11A, Sections 1121A and 1124A.11, or Chapter...
-
1009.6 Areas of refuge
Every required area of refuge shall be accessible from the space it serves by an accessible means of egress....
-
1009.6.3 Size
Such wheelchair spaces shall not reduce the means of egress minimum width or required capacity....
-
1009.6.4 Separation
Areas of refuge in outdoor facilities where exit access is essentially open to the outside....
-
1009.6.5 Two-way communication
Areas of refuge shall be provided with a two-way communication system complying with Sections 1009.8.1 and 1009.8.2.
-
1009.7 Exterior areas for assisted rescue
Exterior areas for assisted rescue shall be accessed by an accessible route from the area served....
-
1009.7.4 Stairways
Stairways that are part of the means of egress for the exterior area for assisted rescue shall provide a minimum clear width of 48 inches (1220 mm) between handrails....
-
1009.8 Two-way communication
A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevators on each accessible floor that is...
-
1009.8.1 System requirements
Two-way communication systems shall provide communication between each required location and the fire command center or a central control point location approved by the fire...
-
1009.8.1.1 Visible communication method
[DSA-AC and HCD 1-AC] A button complying with Section 1138A.4 or Sections 11B-205 and 11B-309 in the area of refuge shall activate both a light in the area of refuge indicating that...