Standing supports shall provide continuous support throughout use of the diagnostic equipment and shall comply with M305.3.
Search Results "Patient Room"
-
M305.3 Standing Supports
-
M303.2.3.3 Side Entry
Where wheelchair space entry is only from the side, the wheelchair space shall be 60 inches (1525 mm) deep minimum.
-
M303.2.3.2 Pass Through Entry
Where wheelchair space entry and exit permits pass through from one end to the other, the wheelchair space shall be 40 inches deep (1015 mm) minimum.
-
M304.2.2 Standing Supports
Standing supports shall be provided on two sides of the standing surface and shall comply with M305.3. EXCEPTION: Diagnostic equipment with entry and exit permitting pass-through...
-
M305.3 Standing Supports (Section-by-Section Analysis)
M305.3 provides the technical requirements for standing supports which are required on diagnostic equipment covered by M304. This provision has been reorganized in the final rule...
-
Physical Access
Resources found at http://www.hfcdihp.org/products.html Choosing and Negotiating an Accessible Facility Location Improving Accessibility with Limited...
-
M304.3 Standing Supports
Standing supports shall be provided on each side of the standing surface and shall comply with M305.3.
-
M305.3 Standing Supports
Standing supports shall provide continuous support throughout use of the diagnostic equipment and shall comply with M305.3.
-
b. Exception for Base Support Allowance and Unobstructed Knee and Toe Space
Allowing a maximum base support height of 1.5 inches will provide room for the structural components necessary for an effective base support design and will also be accessible by around...
-
Swimming pools, wading pools, saunas, and steam rooms. (Section-by-Section Analysis)
Swimming pools, wading pools, saunas, and steam rooms....
-
The Presentation Area / Speaker’s Platform Design and Considerations
Both layouts incorporate presentation screens that are easily viewed from all areas of the room....
-
Technical Memorandum TM 2012-09 Employee Break Rooms
TM 2012-09 Employee Break Rooms Effective Date: January 22, 2013 2012 TAS Reference: 212 and 804 In accordance with TAS 106.5.28, kitchenettes and break rooms are not employee...
-
11B-806.3.2 Notification devices
Visible notification devices shall be provided to alert room occupants of incoming telephone calls and a door knock or bell....
-
11B-806.3.2 Notification devices
Visible notification devices shall be provided to alert room occupants of incoming telephone calls and a door knock or bell....
-
M301.4.2 Clearance Around Base
The base of diagnostic equipment shall provide a clearance 6 inches (150 mm) high minimum measured from the floor and 36 inches (915 mm) deep minimum measured from the edge of the...
-
M301.4.2 Clearance Around Base
The base of the equipment shall provide a clearance 6 inches (150 mm) high minimum measured from the floor and 36 inches (915 mm) deep minimum measured from the edge of the...
-
M301.4.2 Clearance Around Base
[See subsections ...]
- Access Board: Turning Space Size
-
M302.2.5 Unobstructed Transfer (Section-by-Section Analysis)
The final rule retains the requirement for unobstructed transfer, but has been reworded to specify that each transfer surface must provide two unobstructed sides for the patient to transfer...
-
Doors, Doorways, and Gates
In transient lodging facilities, doors and doorways in inaccessible guest rooms are required to provide a clear width of at least 32 inches....
-
M. Turning Space
M. Is there an area in each public restroom in which a person who uses a wheelchair can turn around - either a 60" diameter circle or a "T"-shaped turn area as shown in Figure 3...
-
12162(a)(2)(D)(iv)
(iv) have a restroom usable by an individual who uses a wheelchair.
-
12162(a)(2)(B)(iv)
(iv) have a restroom usable by an individual who uses a wheelchair, only to the extent provided in paragraph (3).