The height of the top of the gripping surface on horizontal standing supports shall be 34 inches (865 mm) minimum and 38 inches (965 mm) maximum above the standing surface.
Search Results "Fixed Equipment"
Commonly Searched Documents
-
M305.3.2.1 Horizontal Position
-
M303.3.3.4 Edge Protection
Ramps with drop offs ½ inch (13 mm) or greater shall provide edge protection 2 inches (50 mm) high minimum on each side with a drop off.
-
M303.3.3.5 Handrails
Ramps with a rise greater than 6 inches (150 mm) shall provide handrails on both sides.
-
Section 1193.33 Accessibility and usability
Section 1193.33 Accessibility and usability Section 1193.33 requires that, where readily achievable, manufacturers must (1) provide a description of the accessibility and...
-
M302.2.5 Unobstructed Transfer (Section-by-Section Analysis)
In the MDE NPRM the Access Board proposed that each transfer side provide unobstructed access to the transfer surface, with an exception to permit temporary obstructions as long as...
-
M303.3.3.5 Handrails
Ramps with a rise greater than 6 inches (150 mm) shall provide handrails on each side.
-
M303.3.3.3 Clear Width
The clear width of ramp runs shall be 36 inches (915 mm) minimum.
-
M303.3.3.1 Running Slope
Ramp runs shall have a running slope not steeper than 1:12.
-
Chapter M1 Application and Administration
[See subsections ...]
- Medical Accessibility LLC
- SPORTS 'N SPOKES
-
Figure M3: Overview of M302 Diagnostic Equipment for Use by a Patient in a Seated Position
[See subsections ...]
-
Exam Tables and Chairs
Exam Tables and Chairs Traditional fixed-height exam tables and chairs (also called treatment tables or procedure tables) are too high for many people with a mobility disability to use...
-
Transfer Surface (M301.2 and M302.2)
The transfer surface is the part of the diagnostic equipment onto which patients who use mobility devices or aids transfer when moving onto and off of the equipment (see defined terms in...
-
M302.4 Lift Compatibility
Diagnostic equipment shall be usable with a patient lift and shall comply with M302.4.1 or M302.4.2....
-
PURPOSE AND LEGAL AUTHORITY
Examples of ICT include computers, information kiosks and transaction machines, telecommunications equipment, multifunction office machines, software, websites, and electronic documents....
-
902.4.1 Clear Floor or Ground Space
902.4.1 Clear Floor or Ground Space. A clear floor space complying with 305 positioned for forward approach shall be provided. Knee and toe clearance complying with 306 shall be...
-
902.4.1 Clear Floor or Ground Space
A clear floor space complying with 305 positioned for forward approach shall be provided. Knee and toe clearance complying with 306 shall be provided, except that knee clearance 24...
-
11B-902.4.1 Clear floor or ground space
A clear floor space complying with Section 11B-305 positioned for forward approach shall be provided. Knee and toe clearance complying with Section 11B-306 shall be provided, except...
-
902.4.1 Clear Floor or Ground Space
A clear floor space complying with 305 positioned for forward approach shall be provided. Knee and toe clearance complying with 306 shall be provided, except that knee clearance 24...
-
11B-902.4.1 Clear floor or ground space
A clear floor space complying with Section 11B-305 positioned for forward approach shall be provided. Knee and toe clearance complying with Section 11B-306 shall be provided, except...
-
I. BACKGROUND
The Plaintiffs’ allegations in the DRC/ERC Litigation include, among other things, not being placed in an accessible inpatient room; being examined on inaccessible equipment which required...
-
II. Summary of the Major Provisions of the Regulatory Action
., fixed route, demand-responsive, and ADA complementary paratransit) service will need to make reasonable modifications/accommodations to policies and practices to ensure program accessibility...