M303.2 would require a wheelchair space to be provided at diagnostic equipment used by patients seated in a wheelchair....
Search Results "Patient Seated in Wheelchair"
-
Wheelchair Spaces (M303.2)
-
Exceptions Considered for Wheelchair Spaces on Raised Platforms
For example, the wheelchair footrests would be allowed to extend beyond the depth of the raised platform and over any edge protection on wheelchair weight scales used by patients seated...
-
Knee and Toe Clearance (M303.2.4)
M303.2.4 would require the depth of wheelchair spaces to include knee and toe clearance of 17 inches minimum and 25 inches maximum....
-
Changes in Level at Entry to Wheelchair Spaces (M303.3)
M303.3 includes technical criteria for changes in level at the entry to a wheelchair space as may occur at wheelchair weight scales with raised platforms....
-
Components (M303.4)
The height of the component and any adjustable feature would have to accommodate patients seated in a wheelchair....
-
Figure M6: M303.2.4 Knee and Toe Clearance
-
5.4.3 Transfer Support Height for M301 and M302
Access Board is considering whether 6 inches minimum and 19 inches maximum above the transfer surface would be an appropriate height for transfer supports on diagnostic equipment used by patients...
-
5.8 Wheelchair Spaces Recommendations for M303 Diagnostic Equipment Used by Patients Seated in a Wheelchair
5.8 Wheelchair Spaces Recommendations for M303 Diagnostic Equipment Used by Patients Seated in a Wheelchair...
-
5.8.1 Wheelchair Spaces on Raised Platforms Recommendations
5.8.1 Wheelchair Spaces on Raised Platforms Recommendations Description: Proposed section M303 provides technical criteria for diagnostic equipment used by patients seated in a wheelchair...
-
5.8.1.1 Clear Platform Size Recommendation
The Wheeled Mobility Anthropometry Project recommends this platform dimension.iv These study findings noted that a 36-inch length accommodates standard manual and power wheelchairs and most...
-
5.8.1.2 Entry to Wheelchair Spaces on Raised Platforms
5.8.1.2 Entry to Wheelchair Spaces on Raised Platforms Recommendations Description: Entry to wheelchair spaces on raised surfaces greater than ¼ inch in height requires a transition...
-
5.8.1.2.1 Ramped Entry Slope Recommendations
5.8.1.2.1 Ramped Entry Slope Recommendations The Committee recommends that raised platforms have a ramp with slopes that do not exceed the following: At 0 to 1½ inches, the...
-
5.8.1.2.2 Single Ramped Entry - Edge Protection on the Platform and Platform Sides Recommendations
The limitation on edge protection height will reduce the possibility that the edge protection will interfere with the patient’s footrest. 5.8.1.2.2 Single Ramp Scale with Edge Protection...
-
5.8.1.2.3 Double Ramped Entry - Edge Protection on the Platform sides Recommendations
5.8.1.2.3 Double Ramped Entry - Edge Protection on the Platform sides Recommendations The Committee recommends a minimum two-inch high edge protection on both sides of the...
-
5.8.1.2.4 Edge Protection on Platforms 1½ inches or less in Height Recommendations
5.8.1.2.4 Edge Protection on Platforms 1½ inches or less in Height Recommendations The Committee recommends that no edge protection be required on platforms of 1½ inches or less...
-
5.8.2 Knee and Toe Clearance Recommendations under Breast Platform Recommendations
seated in a wheelchair....
-
5.8.2.1 Height of Breast Platform at Time of Measurement
When the top of the breast platform is at the height of the patient’s breasts, there must be sufficient clearance at the height of the patient’s knees, as is shown in Figure 5.8.2.1....
-
5.8.2.2 Knee Clearance Depth at 27” Above the Ground
5.8.2.2 Knee Clearance Depth at 27” Above the Ground The Committee recommends increasing the knee clearance at 27 inches above the ground to 18 inches minimum.
-
5.8.2.3 Overall Knee and Toe Clearance Recommendation
5.8.2.3 Overall Knee and Toe Clearance Recommendation The Committee recommends increasing the overall knee and toe space to 28 inches minimum. Rationale for the...
-
5.8.2.4 Unobstructed Floor Space Recommendation
While discussing these issues, the Committee also considered positioning methods for patients using wheelchairs....
-
5.8.2.5 Toe Height Recommendation
Looking further at female-specific toe height data, the 95th percentile toe height is 13 inches for manual wheelchair users and 16.1 inches for power wheelchair users.vi As such, the subcommittee...
-
5.8.2.6 Clearance Depth at Toe Height above the ground Recommendation
5.8.2.6 Clearance Depth at Toe Height above the ground Recommendation The Committee recommends 22 inches minimum clearance depth at toe height. Rationale for...
-
5.8.2.7 Base Support Allowance Recommendation
It does obstruct the floor space in front of the gantry and, thus, may limit how close a wheelchair can get to the equipment....
-
5.8.2.8 Knee and Toe Clearance Recommendations Summary
5.8.2.8 Knee and Toe Clearance Recommendations Summary Ultimately, all of the knee and toe clearance recommendations in sections 5.8.2.1 – 5.8.2.7 are summarized below, in Figure...