During use, the tops of transfer support gripping surfaces shall be 6 inches (150 mm) minimum and 19 inches (485 mm) maximum higher than the top of the associated uncompressed transfer surface...
Search Results "Transfer Support"
-
M305.2.3 Height
-
M305.2.4 Cross Section
Transfer supports shall have a cross section complying with 305.2.4.1 or 305.2.4.2....
-
M305.2.4.1 Circular Cross Section
Transfer supports with circular cross sections shall have an outside diameter of 1 ¼ inches (32 mm) minimum and 2 inches (51 mm) maximum....
-
M305.2.4.2 Non-Circular Cross Section
Transfer supports with non-circular cross sections shall have a cross-section dimension of 2 inches (51 mm) maximum and a perimeter dimension of 4 inches (100 mm) minimum and 4.8 inches...
-
M305.2.5 Surface Hazards
Transfer supports and surfaces adjacent to transfer supports shall be free of sharp or abrasive components and shall have eased edges....
-
M305.2.6 Gripping Surface
Transfer support gripping surfaces shall be continuous along their length and shall not be obstructed along their tops or sides....
-
M305.2.7 Clearance
Clearance between the transfer support gripping surface and adjacent surfaces or obstructions shall be 1 ½ inches (38 mm) minimum....
-
M305.2.8 Fittings
Transfer supports shall not rotate within their fittings when in place for transfer....
-
2004 ADA and ABA Accessibility Guidelines
The following technical criteria in the proposed standards are based on the 2004 ADA and ABA Accessibility Guidelines: • Height of transfer surfaces on diagnostic equipment used by patients...
-
Transfer Supports (M301.3.1, M302.3.1, and M305.2)
M301.3.1 and M302.3.1 would require transfer supports to be provided for use with the transfer sides....
-
Additional Technical Criteria Considered for Transfer Supports
As discussed below, the Access Board is considering whether additional technical criteria would be appropriate for transfer supports....
-
Location and Size
onto the equipment, and that the supports be repositionable to permit transfer...
-
Height
The Access Board is considering whether 6 inches minimum and 19 inches maximum above the transfer surface would be an appropriate height for transfer supports on diagnostic equipment used...
-
Cross Section of Gripping Surfaces
The Access Board is considering whether the above cross section dimensions would be appropriate for the gripping surfaces of transfer supports on diagnostic equipment used by patients in...
-
Clearances Around Gripping Surfaces
The Access Board is considering whether 1½ inches minimum clearance around the gripping surface would be appropriate for transfer supports on diagnostic equipment used by patients in a supine...
-
M305 Supports
M305 provides the technical criteria for transfer supports and standing supports....
-
Transfer Supports
Transfer Supports A means of support is required when transferring into the entry or seat of a play component....
-
5.4 Transfer Supports Recommendations
5.4 Transfer Supports Recommendations...
-
5.4.1 Transfer Support Location for M301 and M302
5.4.1 Transfer Support Location for M301 and M302 Description: Transfer supports assist individuals while making transfers on to the transfer area....
-
5.4.1.1 Transfer Support Location Recommendation for Stretchers
5.4.1.1 Transfer Support Location Recommendation for Stretchers For Stretchers, the transfer surface is oriented along the long side of the surface....
-
5.4.1.2 Transfer and Positioning Support Location Recommendations for Imaging Equipment with Transfer Surfaces
transfer supports on tables with transfer depths of less than or equal to 24 inches and positioning supports for transfer depths greater than 24 inches....
-
5.4.2 Transfer Support Length for M301 and M302
5.4.2 Transfer Support Length for M301 and M302 Description: Transfer support length applies to the gripping surface of the support, that portion of the support used to grasp or maintain...
-
5.4.2.1 Transfer Support Length Recommendation for Stretchers
5.4.2.1 Transfer Support Length Recommendation for Stretchers On Stretchers, the transfer surface is oriented along the long dimension of the surface on which patients are positioned...
-
5.4.2.2 Transfer and Positioning Support Length Recommendations for Imaging Equipment with Transfer Surfaces
5.4.2.2 Transfer and Positioning Support Length Recommendations for Imaging Equipment with Transfer Surfaces On imaging equipment with transfer surfaces, the transfer surface is oriented...