Call buttons shall have square shoulders, be ¾ inch (19.1 mm) minimum in the smallest dimension and shall be raised 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm) above the surrounding...
Search Results "Hall Call Console"
Commonly Searched Documents
-
11B-407.2.1.2 Size and shape
-
Hall Call Buttons [4.10.3]
These specifications apply to all hall call buttons provided, including those that serve cars that operate independently from others in the same bank or lobby....
-
11B-703.7.2.1 International Symbol of Accessibility
On the accessibility function button on hall call consoles in a destination-oriented elevator system the International Symbol of Accessibility shall be a white symbol on a black background...
-
11B-409.2 Call buttons
Call buttons shall be ¾ inch (19.1 mm) minimum in the smallest dimension and shall comply with Section 11B-309....
-
Height: ADA Standard Section 407.2.1.1
Section 407.2.1.1 covers the current ADA Standards for the height of the elevator call controls.
-
11B-411.2.1.2.5 Audio output
Auditory volume shall be at least 10 dB above ambient sound level, but shall not exceed 80 dB, measured 36 inches (914 mm) in front of the console....
-
11B-411.2.1.2.5 Audio output
Auditory volume shall be at least 10 dB above ambient sound level, but shall not exceed 80 dB, measured 36 inches (914 mm) in front of the console....
-
11B-411.2.1.3.4 Position
Display screens and touch screens shall be positioned so glare is reduced on the screen. Keypads or buttons shall slope away from the user at 15 to 25 degrees from the vertical...
-
11B-411.2.1.3.4 Position
Display screens and touch screens shall be positioned so glare is reduced on the screen. Keypads or buttons shall slope away from the user at 15 to 25 degrees from the vertical...
-
11B-411.2.1.2.5 Audio output
Auditory volume shall be at least 10 dB above ambient sound level, but shall not exceed 80 dB, measured 36 inches (914 mm) in front of the console....
-
11B-407.2.1.6 Keypads
ETA Editor's Note Lacking certain Exceptions allowed by 2010 ADA Standards, and imposing additional requirements regarding call buttons, the preceding CBC requirements pertaining to...
-
11B-411.1.2 Car designations
Clarifies requirements that each elevator capable of responding to a hall call console shall have a unique alphabetic designation....
-
Location: ADA Standard Section 407.2.1.4
Section 407.2.1.4 covers the current ADA Standards for the location of elevator call controls.
-
Signals: ADA Standard Section 407.2.1.5
Section 407.2.1.5 covers the current ADA Standards for elevator call control signals.
-
11B-407.2.2.2 Visible signals
Signals shall be visible from the floor area adjacent to the hall call button. Exceptions: Reserved. Reserved. [2010 ADA Standards] 2....
-
11B-407.2.1.1 Height
Call buttons and keypads shall be located within one of the reach ranges specified in Section 11B-308, measured to the centerline of the highest operable part. Exception: Reserved....
-
Keypads: ADA Standard Section 407.2.1.6
Section 407.2.1.6 covers the current ADA Standards for elevator keypads.
- Figure 407.2.2.2 Visible Hall Signals – Drawing from the U.S. Access Board
-
Hall Signals: ADA Standard Section 408.2.2
Section 408.2.2: covers the current ADA Standards for limited-use/limited-application elevator hall signals.
-
11B-411.2.1.3.1 Keypad call console arrangement
Where keypad call consoles are provided, the display screen shall be located directly above the keypad....
-
11B-411.2.1.3.1 Keypad call console arrangement
Where keypad call consoles are provided, the display screen shall be located directly above the keypad....
-
11B-411.2.1.3.1 Keypad call console arrangement
Where keypad call consoles are provided, the display screen shall be located directly above the keypad....
-
Visible Signals: ADA Standard Section 407.2.2.2
Section 407.2.2.2 covers the current ADA Standards for elevator visible signals.
-
4.10.3 Hall Call Buttons
Call buttons in elevator lobbies and halls shall be centered at 42 in (1065 mm) above the floor....