5.8.2 Knee and Toe Clearance Under Breast Platform. The overall knee and toe space should be increased to a minimum of 28 inches deep, from the initially proposed 25 inch absolute...
Search Results "MDE: Medical Diagnostic Equipment"
Commonly Searched Documents
-
5.8.2 Knee and Toe Clearance Under Breast Platform
-
5.8.2.5 Toe Height
5.8.2.5 Toe Height. The toe height should be 18 inches minimum, measured above the ground when the top of the breast platform is 34 inches above the ground.
-
5.8.2.7 Base Support Allowance
5.8.2.7 Base Support Allowance. Base support is permitted to obstruct the clear floor space if it fits within the allowed base support volume. Base supports can be a maximum of 1½...
-
5.8.2.2 Knee Clearance Depth at 27” Above the Ground
5.8.2.2 Knee Clearance Depth at 27” Above the Ground. The knee clearance should be increased at 27 inches above the ground to 18 inches minimum.
-
5.8.2.5 Toe Height Recommendation
5.8.2.5 Toe Height Recommendation The Committee recommends increasing the toe height to 18 inches minimum, measured above the ground when the top of the breast platform is 34...
-
5.8.2.2 Knee Clearance Depth at 27” Above the Ground
5.8.2.2 Knee Clearance Depth at 27” Above the Ground The Committee recommends increasing the knee clearance at 27 inches above the ground to 18 inches minimum.
-
5.8.2.4 Unobstructed Floor Space
5.8.2.4 Unobstructed Floor Space. The unobstructed floor space in front of the base support should be a minimum of 17 inches deep.
-
5.8.3.1 Breast Platform Height
5.8.3.1 Breast Platform Height. The height of the top of the breast platform should be decreased to 26 inches above the floor. The upper height range for the breast platform was not...
-
5.8.2.6 Clearance Depth at Toe Height Above the Ground
5.8.2.6 Clearance Depth at Toe Height Above the Ground. The toe clearance depth should be 22 inches minimum at toe height.
-
5.8.3 Breast Platform
5.8.3 Breast Platform
-
5.8.2.3 Overall Knee and Toe Clearance Recommendation
5.8.2.3 Overall Knee and Toe Clearance Recommendation The Committee recommends increasing the overall knee and toe space to 28 inches minimum. Rationale for the...
-
5.8.2.6 Clearance Depth at Toe Height above the ground Recommendation
5.8.2.6 Clearance Depth at Toe Height above the ground Recommendation The Committee recommends 22 inches minimum clearance depth at toe height. Rationale for...
-
5.8.2.3 Overall Knee and Toe Clearance
5.8.2.3 Overall Knee and Toe Clearance. The overall knee and toe space should be increased to a minimum of 28 inches.
-
Figure M6: M303.2.4 Knee and Toe Clearance
[See subsections ...]
- Brewer Access™ High-Low Exam Table
- Midmark 641 Barrier-Free® Power Procedures Chair
- Brewer Access™ High-Low Exam Table 700
-
Medical Care and Long-Term Care Facilities: ADA Standard Section 805
[See subsections ...]
- Defining and Delivering Disability-Competent Care - The Lived Experience Of Disability
-
5.8.2.1 Height of Breast Platform at Time of Measurement
This shape varies across different pieces of equipment, and breast platforms do not have standard features that can be used to define the required knee clearance space underneath the breast...
-
Typical Transfer Techniques: Staff Assistance and Patient Lifts
The provider should ask the patient if he or she needs assistance, and if so, what is the best way to help and what extra equipment, if any, is needed....
-
Work Area Equipment
As used in this document, this term shall apply only to equipment that is permanently installed or built-in in employee work areas....
-
WORK AREA EQUIPMENT
As used in this document, this term shall apply only to equipment that is permanently installed or built-in in employee work areas....
-
M303.3.3.2 Cross Slope
The cross slope of ramp runs shall not be steeper than 1:48.