Breast Platform [M303.4.1] Recommendation: The final recommendation for the minimum height of the breast platform is 26 inches from the floor to the top of the breast platform....
Search Results "Breast Platform"
Commonly Searched Documents
-
Breast Platform [M303.4.1]
-
M303.4.1 Breast Platforms
The height of the breast platform shall be 30 inches (760 mm) high minimum and 42 inches (1065 mm) high maximum above the floor when in use by a patient seated in a wheelchair....
-
M303.4.1 Breast Platform Adjustability
Breast platforms shall be continuously adjustable from a low height of 26 inches (660 mm) to a high height of 42 inches (1065 mm) above the floor....
-
M303.4.1 Breast Platform Adjustability (Section-by-Section Analysis)
The MDE NPRM proposed a mammography breast platform height range of 30 inches high minimum and 42 inches high maximum above the floor....
-
4. Breast Platform Adjustability
Additionally, the Access Board proposed specific technical requirements for breast platforms of mammography equipment....
-
U.S. Access Board Medical Diagnostic Equipment Mammography Subcommittee Report:
U.S. Access Board Medical Diagnostic Equipment Mammography Subcommittee Report: Final Recommendations on Equipment Criteria
-
5.8.3 Breast Platform
5.8.3 Breast Platform...
-
5.8.3 Breast Platform Recommendations
5.8.3 Breast Platform Recommendations Description: In addition to providing knee and toe clearance at the breast platform (see 5.8.2 Knee and Toe Clearance Recommendations under Breast...
-
M303.2.4.1 Breast Platforms
Wheelchair spaces beneath breast platforms shall comply with M303.2.4.1....
-
5.8.3.1 Breast Platform Height
5.8.3.1 Breast Platform Height. The height of the top of the breast platform should be decreased to 26 inches above the floor....
-
5.8.3.1 Breast Platform Height Recommendations
5.8.3.1 Breast Platform Height Recommendations The Committee recommends decreasing the minimum height of the top of the breast platform to 26 inches above the floor....
-
Platform Lifts: ADA Standard Section 410
Section 410 covers the current ADA Standards for platform lifts.
-
Platform to Runway Clearance: ADA Standard Section 410.4
Section 410.4 covers the current ADA Standards for the required clearance between the platform and any runway landing.
-
2. Equipment Clearances for Breast Platforms
a breast platform would be 25 inches deep (proposed M303.2.4)....
-
Platform Edges: ADA Standard Section 705.2
Detectable warning surfaces at platform boarding edges shall be 24 inches (610 mm) wide and shall extend the full length of the public use areas of the platform....
-
5.8.2.1 Height of Breast Platform at Time of Measurement
5.8.2.1 Height of Breast Platform at Time of Measurement Recommendation The Committee recommends measuring all knee and toe clearances when the top of the breast platform is set at...
-
5.8.2 Knee and Toe Clearance Under Breast Platform
5.8.2 Knee and Toe Clearance Under Breast Platform....
-
5.8.2.1 Height of Breast Platform At Time of Measurement
5.8.2.1 Height of Breast Platform At Time of Measurement. All knee and toe clearances should be measured when the top of the breast platform is set at 34 inches above the floor....
-
5.8.2 Knee and Toe Clearance Recommendations under Breast Platform Recommendations
5.8.2 Knee and Toe Clearance Recommendations under Breast Platform Recommendations Description: The knee and toe clearance under the breast platform applies to mammography equipment for...
-
Platform Lifts: ADA Standard Section 206.7
Section 206.7 covers scoping requirements in the most current ADA Standards for accessible routes to platform lifts.
-
Platform to Hoistway Clearance: ADA Standard Section 407.4.3
Section 407.4.3 covers the current ADA Standards for the required clearance between the elevator car platform and the hoistway landing.
-
Transfer Platform: ADA Standard Section 1009.5.1
A transfer platform shall be provided at the head of each transfer system....
-
Platform to Hoistway Clearance: ADA Standard Section 409.4.3
Section 409.4.2 covers the ADA Standards for the required clearance between the car platform and the hoistway landing in private residence elevators.
-
M303.4 Components
Breast platforms shall comply with M303.4.1....