Comment. Several commenters from the building industry objected to the specification for a minimum clear headroom of 80 inches. The commenters stated that standard doors provide a...
Search Results "Safe Harbor (FHA)"
Commonly Searched Documents
-
Minimum Clear Headroom
-
1(4) Accessible entrance
(4) Accessible entrance. An entrance that complies with ANSI 4.14 meets section 100.205(a).
-
Section 2. Multistory dwelling unit
"Multistory dwelling unit" means a dwelling unit with finished living space located on one floor and the floor or floors immediately above or below it.
-
§100.201 Covered multifamily dwellings
Covered multifamily dwellings means buildings consisting of 4 or more dwelling units if such buildings have one or more elevators; and ground floor dwelling units in other buildings...
-
1.2 Q. Does the Fair Housing Act cover four one-story dwelling units that share common walls and have individual entrances?
A. Yes. The Fair Housing Act applies to all units in buildings consisting of four or more dwelling units if such buildings have one or more elevators; and ground floor dwelling units...
-
2.1 Q. If a building includes three residential dwelling units and one or more commercial spaces, is the building a covered multifamily dwelling under the Fair Housing Act?
A. No. Covered multifamily dwellings are buildings consisting of four or more dwelling units, if such buildings have one or more elevators; and ground floor dwelling units in other...
-
Section 4. Application of the Guidelines
This section states that the design specifications that comprise the final Guidelines apply to all "covered multifamily dwellings" as defined in Section 2 of the Guidelines. Section...
-
Enforcement Mechanisms
In the proposed guidelines, the Department solicited public comment on effective enforcement mechanisms (55 FR 24383-24384). Specifically, the Department requested comment on the...
-
Bathroom Design Illustrations
Comment. A number of commenters from the disability community stated that two of the six bathroom drawings in the preamble to the proposed guidelines (numbers 4 and 6 at 55 FR...
-
First Occupancy
Comment. A number of commenters requested clarification of the determination of "first occupancy" after March 13, 1991. A few commenters referred to the Act's first occupancy...
-
Section 1: Dwellings Subject to the New Construction Requirements of the Fair Housing Act.
The issues addressed in this section concern the types of multifamily dwellings (or portions of such dwellings) designed and constructed for first occupancy after March 13, 1991 that...
-
§100.205(c)(3)(ii)
(ii) Light switches, electrical outlets, thermostats, and other environmental controls in accessible locations;
-
30.1 Q. Would it be acceptable to use removable base cabinets beneath a wall-hung lavatory where a parallel approach is not possible?
A. Yes. The space under and around the cabinet should be finished prior to installation. For example, the tile or other floor finish must extend under the removable base cabinet.
-
7(2)(a)(i)
(i) Sufficient maneuvering space is provided within the bathroom for a person using a wheelchair or other mobility aid to enter and close the door, use the fixtures, reopen the door...
-
7(1)(b)
(b) Clearance between counters and all opposing base cabinets, countertops, appliances or walls is at least 40 inches.
-
7(2)(b)(ii)
(ii) Where the door swings out, a clear space is provided within the bathroom for a person using a wheelchair or other mobility aid to position the wheelchair such that the person is...
-
§100.205(d)
(d) The application of paragraph (c) of this section may be illustrated by the following examples: Example (1): A developer plans to construct a 100 unit condominium apartment...
- ADA Checklist for Existing Facilities
-
7(2)(b)(vii)
(vii) Stall showers in the bathroom may be of any size or configuration. A minimum clear floor space 2'6" wide by 4'0" should be available outside the stall. (See Figure 7(d).) If...
-
(c) Thresholds at patio, deck or balcony doors
The final Guidelines provide that exterior deck, patio, or balcony surfaces should be no more than 1/2 inch below the floor level of the interior of the dwelling unit, unless they...
-
(a) Single-story dwelling units
For single-story dwelling units, the final Guidelines specify the same design specifications as presented in the proposed Option One guidelines, except that design features within...
-
Showers
Comments. Several commenters requested that the final Guidelines provide dimensions on the appropriate width and height of showers and shower doors. Another commenter asked whether...
-
Thresholds at Exterior Doors/Thresholds to Balconies or Decks
Comment. A number of commenters from the building industry objected to the provision of the Option One guidelines that specified that an exterior deck, balcony, patio, or similar...
-
4(5)
(5) Exterior deck, patio, or balcony surfaces are no more than 1/2 inch below the floor level of the interior of the dwelling unit, unless they are constructed of impervious material...