The Midmark 641 Barrier-Free® power procedures chair offers versatile positioning, increased accessibility and better patient comfort to help meet these changing demands, allowing you to...
Search Results "Firing Position"
Commonly Searched Documents
- Midmark 641 Barrier-Free® Power Procedures Chair
-
NFPA: ADA Standard Section 105.2.5
Section 105.2.5 of the ADA Standards cover references to the National Fire Protection Association (NFPA).
-
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
[See subsections ...]
-
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
[See subsections ...]
- Brewer Access™ High-Low Exam Table
-
5.6.1 Stirrups for Equipment Used by Patient in Supine, Prone, or Side-Lying Position
5.6.1 Stirrups for Equipment Used by Patient in Supine, Prone, or Side-Lying Position....
-
B. M301 Diagnostic Equipment Used by Patients in a Supine, Prone, or Side-lying Position and M302 Diagnostic Equipment Used by Patients in a Seated Position
In the final rule M301 and M302 provide the technical requirements for diagnostic equipment used in the supine, prone, or side-lying position, and diagnostic equipment used by patients in...
- Brewer Access™ High-Low Exam Table 700
-
5.4.3.1 Positioning Support Height for Imaging Equipment
5.4.3.1 Positioning Support Height for Imaging Equipment. Positioning supports should be positioned 3 to 6 inches above the transfer surface....
- Brewer Assist Power Procedure Table
- Safety Technology: the First 30 Years
-
[F] 907.4.2.2 Height
The height of the manual fire alarm boxes shall be not less than 42 inches (1067 mm) and not more than 48 inches (1219 mm) measured vertically, from the floor level to the highest point...
-
[F] 907.4.2.2 Height
The height of the manual fire alarm boxes shall be not less than 42 inches (1067 mm) and not more than 48 inches (1219 mm) measured vertically, from the floor level to the highest point...
- Pilot Rock Accessible Grills and Fire Rings
-
Activation: ADA Standard Section 809.5.1.2
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
- Brewer Access™ High-Low Exam Table
-
4.3.5 Patient Positions During Diagnostic Imaging
4.3.5 Patient Positions During Diagnostic Imaging Finally, the vast majority of diagnostic imaging exams are conducted while patients are supine, prone, or side-lying on the table....
-
11B-809.5.1.1 Alarm appliances
Where alarm appliances are provided within a residential dwelling unit as part of the building fire alarm system, they shall comply with Chapter 9, Section 907.5.2.3.3....
-
F202.6.5.2 Fire Alarms
Fire alarms shall comply with F215. EXCEPTION: Fire alarms shall not be required to comply with 702 where existing power sources must be upgraded to meet the requirement....
-
M301 Diagnostic Equipment used by Patients in a Supine, Prone, or Side-lying Position (Section-by-Section Analysis)
M301 in the final rule establishes the technical criteria for diagnostic equipment used by patients in a supine, prone, or side-lying position such as, examination tables, imaging tables...
-
Size: ADA Standard Section 407.4.8.1.1
Section 407.4.8.1.1 covers the current ADA Standards for size of visible elevator car position indicators.