703.5.8 Character Spacing. Character spacing shall be measured between the two closest points of adjacent characters, excluding word spaces. Spacing between individual characters...
Search Results "Stair Lift"
-
703.5.8 Character Spacing
-
703.5.8 Character Spacing
Character spacing shall be measured between the two closest points of adjacent characters, excluding word spaces. Spacing between individual characters shall be 10 percent minimum...
-
703.5.4 Character Proportions
703.5.4 Character Proportions. Characters shall be selected from fonts where the width of the uppercase letter "O" is 55 percent minimum and 110 percent maximum of the height of the...
-
703.5.4 Character Proportions
Characters shall be selected from fonts where the width of the uppercase letter "O" is 55 percent minimum and 110 percent maximum of the height of the uppercase letter "I".
-
§ 37.42(d)
(d) Before constructing or altering a platform at a station covered by paragraph (c) of this section, at which a railroad proposes to use a means other than level-entry boarding, the...
-
§ 37.42(d)
(d) Before constructing or altering a platform at a station covered by paragraph (c) of this section, at which a railroad proposes to use a means other than level-entry boarding, the...
-
T202 Accessible Means of Boarding and Alighting
Provision of accessible boarding and alighting may be accomplished through the use of ramps and bridgeplates, lifts, or level boarding and alighting systems that meet the technical requirements...
-
1009.2 Continuity and components
Platform lifts complying with Section 1009.5, and Chapter 11A, Section 1124A, or Chapter 11B, Sections 11B-207, 11B-207.2 and 11B-410 as applicable....
-
F216.1 General
Signs shall be provided in accordance with F216 and shall comply with 703. EXCEPTIONS: 1. Building directories, menus, seat and row designations in assembly areas, occupant names,...
-
703.5.3 Style
Characters shall be conventional in form. Characters shall not be italic, oblique, script, highly decorative, or of other unusual forms.
-
11B-703.1 General
Signs shall comply with Section 11B-703. Where both visual and tactile characters are required, either one sign with both visual and tactile characters, or two separate signs, one...
-
11B-703.5.3 Style
Characters shall be conventional in form. Characters shall not be italic, oblique, script, highly decorative, or of other unusual forms. [S.H. Visual character style not addressed...
-
703.1 General
Signs shall comply with 703. Where both visual and tactile characters are required, either one sign with both visual and tactile characters, or two separate signs, one with visual,...
-
703.5.6 Height from Finish Floor or Ground
Visual characters shall be 40 inches (1015 mm) minimum above the finish floor or ground. EXCEPTION: Visual characters indicating elevator car controls shall not be required to...
-
703.4.2 Location
Where a tactile sign is provided at a door, the sign shall be located alongside the door at the latch side. Where a tactile sign is provided at double doors with one active leaf, the...
-
Raised and Brailled Characters and Pictorial Symbol Signs [4.30.4]
Raised and Brailled Characters and Pictorial Symbol Signs [4.30.4] Raised characters are required to have simple, preferably no, serif. Fancy serif styles make tactile reading...
-
4.1.2(7) Building Signage
(7) Building Signage. Signs which designate permanent rooms and spaces shall comply with 4.30.1, 4.30.4, 4.30.5 and 4.30.6. Other signs which provide direction to, or information...
-
F216.1 General
Signs shall be provided in accordance with F216 and shall comply with 703.
-
4.1.1(7)
(7) All signs shall comply with 4.30. Elements and spaces of accessible facilities which shall be identified by the International Symbol of Accessibility are: (a) Parking spaces...
-
11B-703.1 General
11B-703.1 General. Signs shall comply with Section 11B-703. Where both visual and tactile characters are required, either one sign with both visual and tactile characters, or two...
-
11B-703.5.3 Style
11B-703.5.3 Style. Characters shall be conventional in form. Characters shall not be italic, oblique, script, highly decorative, or of other unusual forms.
-
11B-703.5.3 Style
Characters shall be conventional in form. Characters shall not be italic, oblique, script, highly decorative, or of other unusual forms.
-
11B-703.1 General
Signs shall comply with Section 11B-703. Where both visual and tactile characters are required, either one sign with both visual and tactile characters, or two separate signs, one...
-
216.1 General
Signs shall be provided in accordance with 216 and shall comply with 703. EXCEPTIONS: 1. Building directories, menus, seat and row designations in assembly areas, occupant...