5.8.2 Knee and Toe Clearance Under Breast Platform. The overall knee and toe space should be increased to a minimum of 28 inches deep, from the initially proposed 25 inch absolute...
Search Results "Patient Position"
-
5.8.2 Knee and Toe Clearance Under Breast Platform
-
5.8.2.5 Toe Height
5.8.2.5 Toe Height. The toe height should be 18 inches minimum, measured above the ground when the top of the breast platform is 34 inches above the ground.
-
5.8.2.7 Base Support Allowance
5.8.2.7 Base Support Allowance. Base support is permitted to obstruct the clear floor space if it fits within the allowed base support volume. Base supports can be a maximum of 1½...
-
5.8.2.2 Knee Clearance Depth at 27” Above the Ground
5.8.2.2 Knee Clearance Depth at 27” Above the Ground. The knee clearance should be increased at 27 inches above the ground to 18 inches minimum.
-
5.8.2.2 Knee Clearance Depth at 27” Above the Ground
5.8.2.2 Knee Clearance Depth at 27” Above the Ground The Committee recommends increasing the knee clearance at 27 inches above the ground to 18 inches minimum.
-
5.8.2.4 Unobstructed Floor Space
5.8.2.4 Unobstructed Floor Space. The unobstructed floor space in front of the base support should be a minimum of 17 inches deep.
-
5.8.3.1 Breast Platform Height
5.8.3.1 Breast Platform Height. The height of the top of the breast platform should be decreased to 26 inches above the floor. The upper height range for the breast platform was not...
-
5.8.2.8 Knee and Toe Clearance Recommendations Summary
5.8.2.8 Knee and Toe Clearance Recommendations Summary Ultimately, all of the knee and toe clearance recommendations in sections 5.8.2.1 – 5.8.2.7 are summarized below, in Figure...
-
5.8.2.6 Clearance Depth at Toe Height Above the Ground
5.8.2.6 Clearance Depth at Toe Height Above the Ground. The toe clearance depth should be 22 inches minimum at toe height.
-
5.8.3 Breast Platform
5.8.3 Breast Platform
-
5.8.2.3 Overall Knee and Toe Clearance Recommendation
5.8.2.3 Overall Knee and Toe Clearance Recommendation The Committee recommends increasing the overall knee and toe space to 28 inches minimum. Rationale for the...
-
5.8.2.6 Clearance Depth at Toe Height above the ground Recommendation
5.8.2.6 Clearance Depth at Toe Height above the ground Recommendation The Committee recommends 22 inches minimum clearance depth at toe height. Rationale for...
-
5.8.2.3 Overall Knee and Toe Clearance
5.8.2.3 Overall Knee and Toe Clearance. The overall knee and toe space should be increased to a minimum of 28 inches.
-
Figure M6: M303.2.4 Knee and Toe Clearance
[See subsections ...]
-
11B-305.5 Position
Unless otherwise specified, clear floor or ground space shall be positioned for either forward or parallel approach to an element. ...
-
11B-305.5 Position
Unless otherwise specified, clear floor or ground space shall be positioned for either forward or parallel approach to an element. ...
-
3. Exception to Ramp Running Slope
The Access Board agrees with the MDE Advisory Committee that additional allowances in the slope of ramp runs of diagnostic equipment used by patients seated in a wheelchair with raised platforms...
-
11B-411.2.1.3.4 Position
Display screens and touch screens shall be positioned so glare is reduced on the screen. Keypads or buttons shall slope away from the user at 15 to 25 degrees from the vertical plane....
-
11B-411.2.1.3.4 Position
Display screens and touch screens shall be positioned so glare is reduced on the screen. Keypads or buttons shall slope away from the user at 15 to 25 degrees from the vertical plane....
-
WMD POSITIONS FOR TRANSFER
WMD POSITIONS FOR TRANSFER The design of the corner radii allows closest possible position for wheelchair transfers, minimizing potential gaps and improving the patient’s ability to transfer...
-
M303.3.3.2 Cross Slope
The cross slope of ramp runs shall not be steeper than 1:48.
-
M303.3.3 Ramped
Changes in level greater than ½ inch (13 mm) high shall be ramped and shall comply with M303.3.3.
-
M303.3.3 Ramped (Section-by-Section Analysis)
The MDE NPRM proposed that for equipment with a change in level at the entry of a wheelchair space, level changes greater than ½ inch high would be required to be ramped and comply...
-
5.8.1.2.1 Ramped Entry Slope Recommendations
5.8.1.2.1 Ramped Entry Slope Recommendations The Committee recommends that raised platforms have a ramp with slopes that do not exceed the following: At 0 to 1½ inches, the...