In transient lodging facilities, entrances, doors, and doorways providing user passage into and within guest rooms that are not required to provide mobility features complying with 806.2...
Search Results "End-Opening Door"
Commonly Searched Documents
-
206.5.3 Transient Lodging Facilities
-
Can handrails overlap door maneuvering clearances?
No, door maneuvering clearances must be free of any overlapping objects, even those providing knee and toe clearance, which can interfere with maneuvering at doors and doorways....
-
7b.
Is the door hardware (e.g., lever, pull, push, panic bar) usable with one hand, without tight grasping, pinching, or twisting of the wrist, to allow people who may not be able to easily...
-
407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish floor....
-
407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish floor....
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor....
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor....
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor....
-
A. Movie Basics, Captioning, and Audio Description Generally
Currently, some movie theaters exhibit open-captioned films at certain limited showings....
-
Horton Automatics EasyAccessยฎ Series 7100 for ADA Low Energy Applications
Requires the Premium User plan or above. (Login or upgrade your account!)
-
ยง 38.125(b)(7) Platform gaps
Any openings between the lift platform surface and the raised barriers shall not exceed 5/8 inch wide....
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish floor....
-
D4. Door Clearance
On the pull side of the door, is there at least 18 inches clearance provided to the side of the latch if the door is not automatic or power-operated?...
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....
-
407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....