Call buttons and keypads shall be located within one of the reach ranges specified in Section 11B-308, measured to the centerline of the highest operable part. Exception:...
Search Results "Freight Elevator"
-
11B-407.2.1.1 Height
-
11B-411.2.1.4 Additional features
Hall call console additional features, if provided, shall comply with Sections 11B-309 and 11B-411.2.1.4.
-
11B-409.4.4 Leveling
Each car shall automatically stop at a floor landing within a tolerance of ½ inch (12.7 mm) under rated loading to zero loading conditions.
-
11B-411.2.1 Hall call consoles
Hall call consoles shall comply with Sections 11B-411.2.1 and 11B-309.
-
11B-411.2.1.3 Arrangement
Hall call console arrangement of required features shall comply with Section 11B-411.2.1.3.
-
11B-407.4.8.2 Audible indicators
Audible indicators shall comply with Section 11B-407.4.8.2.
-
11B-411.4.7.2 Location
Raised characters or symbols and Braille designations shall comply with Section 11B-407.4.7.1.2.
-
11B-411.2.1.3 Arrangement
Hall call console arrangement of required features shall comply with Section 11B-411.2.1.3.
-
11B-411.2.1.4 Additional features
Hall call console additional features, if provided, shall comply with Sections 11B-309 and 11B-411.2.1.4.
-
11B-407.4.8.2 Audible indicators
Audible indicators shall comply with Section 11B-407.4.8.2.
-
11B-409.4.4 Leveling
Each car shall automatically stop at a floor landing within a tolerance of ½ inch (12.7 mm) under rated loading to zero loading conditions.
-
11B-407.4.3 Platform to hoistway clearance
The clearance between the car platform sill and the edge of any hoistway landing shall be 1¼ inch (32 mm) maximum.
-
11B-411.2.1 Hall call consoles
Hall call consoles shall comply with Sections 11B-411.2.1 and 11B-309.
-
11B-407.2.1.1 Height
Call buttons and keypads shall be located within one of the reach ranges specified in Section 11B-308, measured to the centerline of the highest operable part. Exception:...
-
1008.2.1 Ground Level and Elevated Play Components
1008.2.1 Ground Level and Elevated Play Components....
-
407.4.8.2.1 Signal Type
EXCEPTION: For elevators other than destination-oriented elevators that have a rated speed of 200 feet per minute (1 m/s) or less, a non-verbal audible signal with a frequency of 1500 Hz...
-
407.4.8.2.1 Signal Type
[ECTCR UFAS 4.10.13] EXCEPTION: For elevators other than destination-oriented elevators that have a rated speed of 200 feet per minute (1 m/s) or less, a non-verbal audible signal with...
-
407.4.8.2.1 Signal Type
EXCEPTION: For elevators other than destination-oriented elevators that have a rated speed of 200 feet per minute (1 m/s) or less, a non-verbal audible signal with a frequency of 1500 Hz...
-
1008.2.1 Ground Level and Elevated Play Components
Transfer systems complying with 1008.3 shall be permitted to connect elevated play components except where 20 or more elevated play components are provided no more than 25 percent of the...
-
1008.2.1 Ground Level and Elevated Play Components
Transfer systems complying with 1008.3 shall be permitted to connect elevated play components except where 20 or more elevated play components are provided no more than 25 percent of the...
-
11B-233.3.1.2.2 Non-elevator buildings
Ground floor residential dwelling units in non-elevator buildings shall be adaptable....
-
11B-409.4.6.1 Size
Control buttons shall be ¾ inch (19.1 mm) minimum in their smallest dimension.
-
409.4.6.1 Size
Control buttons shall be 3/4 inch (19 mm) minimum in their smallest dimension.
-
409.4.6.2 Location
Control panels shall be on a side wall, 12 inches (305 mm) minimum from any adjacent wall.