A change to a building or facility that affects or could affect the usability of the building or facility or portion thereof....
Search Results "Fire-Building Surface"
-
Alteration
-
11B-404.2.4.4 Floor or ground surface
Floor or ground surface within required maneuvering clearances shall comply with Section 11B-302....
-
4.13.11(1)
(1) Fire doors shall have the minimum opening force allowable by the appropriate administrative authority....
-
General [4.5.1]
Design guidelines cannot encompass all criteria contributing to the safety of a walking surface....
-
11B-702.1 General
Fire alarm systems shall have permanently installed audible and visible alarms complying with NFPA 72 and Chapter 9, Sections 907.5.2.1 and 907.5.2.3. [2010 ADAS] 702.1 General. ...
-
11B-702.1 General
Fire alarm systems shall have permanently installed audible and visible alarms complying with NFPA 72 and Chapter 9, Sections 907.5.2.1 and 907.5.2.3. [2010 ADAS] 702.1 General....
-
11B-702.1 General
Fire alarm systems shall have permanently installed audible and visible alarms complying with NFPA 72 and Chapter 9, Sections 907.5.2.1 and 907.5.2.3....
-
11B-404.2.9 Door and gate opening force
Fire doors shall have a minimum opening force allowable by the appropriate Administrative Authority....
-
11B-404.2.9 Door and gate opening force
Fire doors shall have a minimum opening force allowable by the appropriate Administrative Authority....
-
11B-902.4 Dining surfaces and work surfaces for children’s use
Accessible dining surfaces and work surfaces for children’s use shall comply with Section 11B-902.4....
-
11B-902.4 Dining surfaces and work surfaces for children’s use
Accessible dining surfaces and work surfaces for children’s use shall comply with Section 11B-902.4....
-
11B-902.4 Dining surfaces and work surfaces for children’s use
Accessible dining surfaces and work surfaces for children’s use shall comply with Section 11B-902.4....
-
Elevators with Standby Power [IBC §1007.4 (2003), §1003.2.13.3 (2000)]
In buildings with four or more stories above or below the level of exit discharge, at least one accessible means of egress must be an elevator with standby power and emergency signaling...
- TelCom Wheelock Wall Mount Chime - 24 VDC 15/75 on Axis Strobe Candela CH70-241575W-FR
-
11B-201.2 Application based on building or facility use
Where a site, building, facility, room, or space contains more than one use, each portion shall comply with the applicable requirements for that use. ...
-
11B-201.2 Application based on building or facility use
Where a site, building, facility, room, or space contains more than one use, each portion shall comply with the applicable requirements for that use....
-
11B-201.2 Application based on building or facility use
Where a site, building, facility, room, or space contains more than one use, each portion shall comply with the applicable requirements for that use....
-
F215.1 General
Where fire alarm systems provide audible alarm coverage, alarms shall comply with F215....
-
215.1 General
Where fire alarm systems provide audible alarm coverage, alarms shall comply with 215....
-
215.1 General
Where fire alarm systems provide audible alarm coverage, alarms shall comply with 215....
-
410.2 Floor Surfaces
Floor surfaces in platform lifts shall comply with 302 and 303....
-
410.2 Floor Surfaces
Floor surfaces in platform lifts shall comply with 302 and 303....
-
R408.4 Tread Surface
R408.4 Tread Surface. Stairway treads shall comply with R302.7. Changes in level are not permitted....
-
F105.2.5 NFPA
Copies of the referenced standards may be obtained from the National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 02169-7471, (http://www.nfpa.org)....