Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1....
Search Results "Hoistway Clearance"
Commonly Searched Documents
-
404.2.4.1 Swinging Doors and Gates
- Boost Your Business - Chapter 12 - Elevators
-
11B-604.8.1.4 Toe clearance
11B-604.8.1.4 Toe clearance....
-
407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish floor.
-
407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.3.5 Door delay
Elevator doors shall remain fully open in response to a car call for 5 seconds minimum. [2010 ADAS] 407.3.5 Door Delay. Elevator doors shall remain fully open in response to a...
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
407.3.5 Door Delay
Elevator doors shall remain fully open in response to a car call for 3 seconds minimum.
-
407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish floor.
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
407.3.5 Door Delay
Elevator doors shall remain fully open in response to a car call for 3 seconds minimum.
-
407.3.3.3 Duration
407.3.3.3 Duration. Door reopening devices shall remain effective for 20 seconds minimum.
-
407.3.5 Door Delay
407.3.5 Door Delay. Elevator doors shall remain fully open in response to a car call for 3 seconds minimum.
-
407.3.3.2 Contact
407.3.3.2 Contact. The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
407.3.3.1 Height
407.3.3.1 Height. The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish...
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
Must elevator doors remain open for 20 seconds?
LULA swing doors, private residence elevator doors, and platform lift gates and doors must remain open for 20 seconds minimum. This does not apply to the doors of passenger elevators...
-
Can elevator doors close sooner than the minimum opening time specified when users activate door close?
User activation of door close (or automatic operation) cannot reduce the initial opening time of doors (3 seconds minimum) or the minimum door signal timing (based on 1.5/ ft/s...
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.5 Door delay
Elevator doors shall remain fully open in response to a car call for 5 seconds minimum. [2010 ADAS] 407.3.5 Door Delay. Elevator doors shall remain fully open in response to a car...
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.