Section 215.3 covers scoping requirements in the current ADA Standards for fire alarm systems in employee work areas.
Search Results "Firing Position"
-
Employee Work Areas: ADA Standard Section 215.3
-
Residential Dwelling Unit Smoke Detection System: ADA Standard Section 809.5.2
Residential dwelling unit smoke detection systems shall comply with NFPA 72 (1999 or 2002 edition) (incorporated by reference, see “Referenced Standards” in Chapter 1).
-
11B-215.3 Employee work areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.1 Exception can be...
-
11B-215.3 Employee work areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.1 Exception can be...
-
M301.2.1 Height
The transfer surface is permitted to be positioned outside of the specified height range when not needed to facilitate transfer....
-
M301.2.1 Adjustability
A low transfer position at a height of 17 inches (430 mm) minimum and 19 inches (485 mm) maximum; B. A high transfer position at 25 inches (635 mm); and C....
-
5.4.2.1 Transfer Support Length for Stretchers
5.4.2.1 Transfer Support Length for Stretchers. Transfer supports on stretchers should be a minimum of 15 inches long.
-
5.4.4.1 Transfer Support Distance from Transfer Surface Recommendation for Stretchers
5.4.4.1 Transfer Support Distance from Transfer Surface Recommendation for Stretchers The Committee recommends locating the transfer support along the long side of the of the...
-
5.3.2.1 Transfer Sides for Stretchers
5.3.2.1 Transfer Sides for Stretchers. The transfer surface shall be located to provide the ability to transfer from a mobility device onto both long sides of the surface.
-
5.4.4.1 Transfer Support Distance from Transfer Surface for Stretchers
5.4.4.1 Transfer Support Distance from Transfer Surface for Stretchers. Transfer supports should be located along the long side of the transfer surface on the opposite side of the...
-
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more
Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm communications system in accordance with...
-
5.3.3 Transfer Sides for Equipment Used by Patients in Seated Position
5.3.3 Transfer Sides for Equipment Used by Patients in Seated Position....
-
5.1.1 Transfer Surface Height Adjustability Recommendation for M301 and M302
Adjustable height MDE, such as exam tables, imaging tables and chairs, will make it possible to position the transfer surface near the height of the seat of the mobility device....
-
M301.2.3 Transfer Surface Transfer Sides
The head and foot ends of the table are likely to have obstructions such as extraction handles, the gantry, or patient positioning devices....
-
5.4.2 Transfer Support Length for M301 and M302
The purpose of a minimum length is to ensure that there is a minimum gripping surface available to support positioning and repositioning during a transfer....
-
809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
907.5.2.3.4 Groups R-2.1, R-3.1 and R-4
are hearing impaired, shall be provided with notification appliances for the hearing impaired installed in accordance with NFPA 72 and which shall [sic] activated upon initiation of the fire...
-
907.5.2.3.4 Groups R-2.1, R-3.1 and R-4
are hearing impaired, shall be provided with notification appliances for the hearing impaired installed in accordance with NFPA 72 and which shall [sic] activated upon initiation of the fire...
-
809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
M305.2.1 Location
Transfer supports shall be located within reach of the transfer surface and shall not obstruct transfer onto or off of the surface when in position....