Elevator doors shall remain fully open in response to a car call for 5 seconds minimum. [2010 ADAS] 407.3.5 Door Delay....
Search Results "Door Closer"
-
11B-407.3.5 Door delay
-
11B-407.3.5 Door delay
Elevator doors shall remain fully open in response to a car call for 5 seconds minimum. [2010 ADA Standards] 407.3.5 Door Delay....
-
4.13.12* AUTOMATIC DOORS AND POWER-ASSISTED DOORS
If an automatic door is used, then it shall comply with American National Standard for Power-Operated Doors, ANSI A156.10-1979....
- Besam PowerSwing Electro-hydraulic Swing Door Operator
-
5.3.5 Doors
Where provided, doors shall comply with ABAAS section 404.Ā The door shall not swing into or otherwise obstruct the clear floor or ground space required by 5.3.2.1....
-
Entrances: ADA Standard Section 206.5.1
Section 206.5.1 covers scoping requirements in the most current ADA Standards for doors, doorways, and gates at entrances.
- DORMA ED700 Low-Energy Swing Door Operator
-
Rooms and Spaces: ADA Standard Section 206.5.2
Section 206.5.2 covers scoping requirements in the most current ADA Standards for accessible routes to rooms and spaces.
-
404.2.4.1 Swinging Doors and Gates
404.2.4.1 Swinging Doors and Gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1....
-
III-7.5125 Doors
IIIā7.5125 Doors (ADAAG §4.1.3(7))....
-
Maneuvering Clearances at Doors [4.13.6]
Maneuvering Clearances at Doors [4.13.6] Pull-side clearance beyond the door swing provides space for a forward reach to door hardware....
- Besam PowerSwing Electro-hydraulic Swing Door Operator BIM
-
Transient Lodging Facilities: ADA Standard Section 206.5.3
Section 206.5.3 covers scoping requirements in the most current ADA Standards for accessible routes to transient lodging facilities.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum....
-
Duration: ADA Standard Section 407.3.3.3
Section 407.3.3.3 covers the current ADA Standards for the duration of an elevators reopening device.
-
404.2.4.1 Swinging Doors and Gates
Table 404.2.4.1 Maneuvering Clearances at Manual Swinging Doors and Gates Type of Use Minimum Maneuvering Clearance Approach Direction Door or Gate Side...
- Besam SW200i Overhead Concealed Swing Door Operator for Dual Egress
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses....
-
Contact: ADA Standard Section 407.3.3.2
Section 407.3.3.2 covers the current ADA Standards for the contact requirements of an elevators reopening device.
-
A4.13.11(2) Sliding or folding doors
(2) Sliding or folding doors: Force applied parallel to the door at the door pull or latch....
-
A4.13.11(2) Sliding or folding doors
(2) Sliding or folding doors: Force applied parallel to the door at the door pull or latch....
-
A4.13.12 Automatic Doors and Power-Assisted Doors
Sliding automatic doors do not need guard rails and are more convenient for wheelchair users and visually impaired people to use....