407.3.3.1 Height. The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish...
Search Results "Elevator Hoistway"
-
407.3.3.1 Height
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
Elevators: ADA Standard Section 206.6
Section 206.6 covers scoping requirements in the most current ADA Standards for accessible routes to elevators.
-
11B-411.2.2 Elevator car identification at elevator landings
Elevator car identification shall comply with Section 11B-411.2.2....
-
11B-411.2.2 Elevator car identification at elevator landings
Elevator car identification shall comply with Section 11B-411.2.2....
-
Preserving elevator access in building where it might not be required.
Each story less than 3000 square feet, so elevator would likely not be required if built new. 2010 Standards 206.2.3, Exception 1. ...
-
11B-206.6 Elevators
Elevators provided for passengers shall comply with Section 11B-407. Where multiple elevators are provided, each elevator shall comply with Section 11B-407....
-
11B-206.6 Elevators
Elevators provided for passengers shall comply with Section 11B-407. Where multiple elevators are provided, each elevator shall comply with Section 11B-407....
- Symmetry Limited Use/Limited Application (LU/LA) Elevator
-
11B-407.4 Elevator car requirements
Elevator cars shall comply with Section 11B-407.4....
-
11B-407.4 Elevator car requirements
Elevator cars shall comply with Section 11B-407.4....
-
11B-411.2 Elevator landing requirements
Elevator landings shall comply with Section 11B-411.2....
-
11B-411.2 Elevator landing requirements
Elevator landings shall comply with Section 11B-411.2....
-
Floor Designations
The proposed rule specified that tactile floor designations at the hoistway be 60 inches above the floor, measured from the baseline of the characters (407.2.4)....
-
Elevators: ADA Standard Section 407
Section 407 covers the current ADA Standards for elevators.
-
11B-411.4.6 Elevator car controls
Where provided, elevator car controls shall comply with Sections 11B-411.4.6 and 11B-309.4....
-
11B-411.4.6 Elevator car controls
Where provided, elevator car controls shall comply with Sections 11B-411.4.6 and 11B-309.4....