Where mirrors are provided the bottom edge of the reflective surface shall be 40 inches (1016 mm) maximum above the finish floor. Where towel bars are provided they shall be...
Search Results "Adaptable Dwelling Unit (FHA)"
-
11B-809.10.8.7 Mirrors and towel bars
-
11B-809.10.8.6 Controls
Faucet controls and operating mechanisms shall comply with Section 11B-309.4.
-
11B-809.10.6.4 Reinforcement for grab bars
Reinforcement for grabs bars shall comply with the following: Continuous reinforcement shall be installed in the walls of showers 30 inches (762 mm) maximum to 38 inches (965 mm)...
-
11B-809.10.8.6 Controls
Faucet controls and operating mechanisms shall comply with Section 11B-309.4.
-
11B-809.10.8.7 Mirrors and towel bars
Where mirrors are provided the bottom edge of the reflective surface shall be 40 inches (1016 mm) maximum above the finish floor. Where towel bars are provided they shall be...
-
11B-809.10.6.4 Reinforcement for grab bars
Reinforcement for grabs bars shall comply with the following: Continuous reinforcement shall be installed in the walls of showers 30 inches (762 mm) maximum to 38 inches (965 mm)...
-
3(2)
(2) Within individual dwelling units, doors intended for user passage through the unit which have a clear opening of at least 32 inches nominal width when the door is open 90 degrees, measured...
-
SECTION 1128A COVERED DWELLING UNITS
SECTION 1128A COVERED DWELLING UNITS...
-
DIVISION IV – DWELLING UNIT FEATURES
DIVISION IV – DWELLING UNIT FEATURES...
-
DIVISION IV – DWELLING UNIT FEATURES
DIVISION IV – DWELLING UNIT FEATURES...
-
11B-206.7.6 Guest rooms and residential dwelling units
Platform lifts shall be permitted to connect levels within transient lodging guest rooms required to provide mobility features complying with Section 11B-806.2 or residential dwelling units...
-
11B-206.7.6 Guest rooms and residential dwelling units
Platform lifts shall be permitted to connect levels within transient lodging guest rooms required to provide mobility features complying with Section 11B-806.2 or residential dwelling units...
-
11B-206.7.6 Guest rooms and residential dwelling units
Platform lifts shall be permitted to connect levels within transient lodging guest rooms required to provide mobility features complying with Section 11B-806.2 or residential dwelling units...
-
Bathroom Design Illustrations
The illustrations are adapted from ANSI A117.1....
-
Residential Dwelling Unit
A unit intended to be used as a residence that is primarily long-term in nature....
-
11B-233.3.1.2.5 Multi-story residential dwelling units in buildings with no elevator
In non-elevator buildings, a minimum of 10 percent but not less than one of the ground floor multi-story residential dwelling units shall be calculated using the total number of multi-story...
-
11B-233.3.1.2.5 Multi-story residential dwelling units in buildings with no elevator
In non-elevator buildings, a minimum of 10 percent but not less than one of the ground floor multi-story residential dwelling units shall be calculated using the total number of multi-story...
-
RESIDENTIAL DWELLING UNIT
[DSA-AC] A unit intended to be used as a residence that is primarily long-term in nature....
-
RESIDENTIAL DWELLING UNIT
[DSA-AC] A unit intended to be used as a residence that is primarily long-term in nature....
-
11B-233.3.2 Residential dwelling units for sale
[2010 ADA Standards] 233.3.2 Residential Dwelling Units for Sale....
-
7.1 Q. Do the new construction requirements of the Fair Housing Act apply to continuing care facilities which incorporate housing, health care and other types of services?
The new construction requirements of the Fair Housing Act would apply to continuing care facilities if the facility includes at least one building with four or more dwelling units....
-
Requirement 3 -- Usable Doors
[See subsections ...]
-
1010.1.7 Thresholds
Thresholds at doorways shall not exceed ¾ inch (19.1 mm) in height above the finished floor or landing for sliding doors serving dwelling units or ½ inch (12.7 mm) above the finished floor...
-
Identification: ADA Standard Section 809.5.5.2
A means for visually identifying a visitor without opening the residential dwelling unit entry door shall be provided and shall allow for a minimum 180 degree range of view....