In standard roll-in type shower compartments, the controls, faucets, and shower spray unit shall be located above the grab bar, but no higher than 48 inches (1220 mm) above the shower floor...
Search Results "Covered Multifamily Dwelling Unit (CBC 11A)"
Commonly Searched Documents
-
608.5.2 Standard Roll-In Type Shower Compartments
-
DSA IR 11B-8 - USE OF PREDETERMINED CONSTRUCTION TOLERANCE GUIDELINES FOR ACCESSIBILITY (with revisions issued through Jan. 2011)
California Department of General Services . Division of the State Architect . Interpretation of Regulations Document IR 11B-8 USE OF PREDETERMINED CONSTRUCTION TOLERANCE...
-
Associated
Associated TAS 604.3.2 allows “associated” grab bars, dispensers, sanitary napkin disposal units, coat hooks, and shelves to overlap the required clearance around an accessible water...
-
608.5.3 Alternate Roll-In Type Shower Compartments
In alternate roll-in type shower compartments, the controls, faucets, and shower spray unit shall be located above the grab bar, but no higher than 48 inches (1220 mm) above the shower floor...
-
3.5.1 General
Use of the ISA for identification of accessible camping units shall conform to 3.2.6. Use of the ISA for identification of accessible picnic units shall conform to 3.3.3....
-
F244.5.3 Routes to Adjacent Recreation Facilities
Where a circulation path connects camping facilities and adjacent recreation facilities, this section requires at least one outdoor recreation access route to connect camping units with...
-
608.5.3 Alternate Roll-In Type Shower Compartments
In alternate roll-in type shower compartments, the controls, faucets, and shower spray unit shall be located above the grab bar, but no higher than 48 inches (1220 mm) above the shower floor...
-
608.5.3 Alternate Roll-In Type Shower Compartments
In alternate roll-in type shower compartments, the controls, faucets, and shower spray unit shall be located above the grab bar, but no higher than 48 inches (1220 mm) above the shower floor...
-
F244.5.2 Routes to and Within Common Use and Public Use Areas
Common use and public use areas serving camping units with mobility features shall provide outdoor recreation access routes in accordance with F244.5.2....
-
11B-233.3.1.2.6.5 Additional requirements.
1. Grab bar reinforcement complying with Sections 11B-809.10.5.2, 11B-809.10.6.4, or 11B-809.10.7.3. 2. Interior door opening width complying with Section 11B-404.3.1. 3....
-
206.7 Platform Lifts, F206.7 Platform Lifts
The floor level of emergency transportable housing units is elevated above the ground....
-
11B-608.5.3 Alternate roll-in type shower compartments
Operable parts of the shower spray unit, including the handle, shall be installed on the side wall of the compartment adjacent to the seat wall 17 inches (432 mm) minimum and 19 inches (...
-
11B-608.5.3 Alternate roll-in type shower compartments
Operable parts of the shower spray unit, including the handle, shall be installed on the side wall of the compartment adjacent to the seat wall 17 inches (432 mm) minimum and 19 inches (...
-
F244.2.3.3 Tent Pads and Tent Platforms
Where provided, at least one tent pad and tent platform shall comply with 1013. Where more than one tent pad and tent platform is provided, at least two tent pads and tent platforms...
-
F244.2.3.2.2 Vehicles Other Than Recreational Vehicles
Where parking spaces are provided for vehicles other than recreational vehicles, at least one parking space shall comply with 1012.3, 1012.4, and 1012.5. Where more than one parking...
-
F245.2.5.2 Parking Spaces
Where provided, at least one parking space shall comply with 1012.3, 1012.4, and 1012.5. Where more than one parking space is provided, at least two parking spaces shall comply with...
-
3.2.5.1 Walk-In Camping
Where walk-in camping is provided, an ORAR connecting the camp living area to the parking area shall be provided in accordance with section 2.0.
-
F244.5.2 Routes to and within Common Use and Public Use Areas
This section requires at least one outdoor recreation access route to connect each camping unit with mobility features with common use and public use areas serving the unit; and at least...
-
F245.4.2 Routes to and within Common Use and Public Use Areas
This section requires at least one outdoor recreation access route to connect each picnic unit with mobility features with common use and public use areas serving the unit; and at least...
- Figure 608.5.3 Alternate Roll-In Type Shower Compartment Control Location – Drawing from the U.S. Access Board
-
Grab Bars [4.20.4] and Controls [4.20.5]
Recommendation: A hose for shower spray units longer than the required minimum of 60 inches is recommended for easier use of the shower spray unit from the seat....
-
F244.3 Outdoor Constructed Features in Common Use and Public Use Areas
Where provided in common use and public use areas that serve camping units with mobility features, at least 20 percent, but not less than one, of each type of outdoor constructed feature...
-
F245.3 Outdoor Constructed Features in Common Use and Public Use Areas
Where provided in common use and public use areas that serve picnic units with mobility features, at least 20 percent, but not less than one, of each type of outdoor constructed feature...