Provisions for the spacing of visual alarms in hallways and corridors generally require one fixture every 100 feet....
Search Results "Visual Indicator (Alarm)"
-
Location and Spacing
-
11B-215.3 Employee work areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.2 can be integrated into the...
-
11B-215.3 Employee work areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.1 Exception can be integrated...
-
11B-215.3 Employee work areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.1 Exception can be integrated...
-
4.1.3(14)
(14) If emergency warning systems are provided, then they shall include both audible alarms and visual alarms complying with 4.28....
-
F215.3 Employee Work Areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with 702 can be integrated into the alarm system....
-
215.3 Employee Work Areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with 702 can be integrated into the alarm system....
-
[F] 907.5.2.3.2 Groups R-1 and R-2.1
Habitable spaces in dwelling units and sleeping units in Group R-1 and R-2.1 occupancies in accordance with Table 907.5.2.3.2 shall be provided with visible alarm notification....
-
215.3 Employee Work Areas
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with 702 can be integrated into the alarm system....
-
907.5.2.3.3 Group R-2
In Group R-2 occupancies required by Section 907 to have a fire alarm system, all dwelling units and sleeping units shall be provided with the capability to support visible alarm notification...
-
[F] 907.5.2.3.4 Group R-2
In Group R-2 occupancies required by Section 907 to have a fire alarm system, all dwelling units and sleeping units shall be provided with the capability to support visible alarm notification...
-
[F] 907.5.2.3.3 Group R-2
visible alarm notification appliances in accordance with NFPA 72....
- Boost Your Business - Chapter 13 - Alarms
-
[F] 907.5.2.3.3 Groups R-1 and R-2.1
Group R-1 and R-2.1 dwelling units or sleeping units in accordance with Table 907.5.2.3.3 shall be provided with a visible alarm notification appliance, activated by both the in-room smoke...
-
[F] 907.5.2.3.2 Groups R-1 and R-2.1
Group R-1 and R-2.1 dwelling units or sleeping units in accordance with Table 907.5.2.3.2 shall be provided with a visible alarm notification appliance, activated by both the in-room smoke...
-
11B-411.4.8.1 Visible indicators
Visible indicators shall comply with Section 11B-411.4.8.1....
-
11B-411.4.8.1 Visible indicators
Visible indicators shall comply with Section 11B-411.4.8.1....
-
Intensity
Intensity To be effective, a visual signal (or its reflection from adjacent walls and ceiling) must be of an intensity that will raise the overall light level sharply, but not be so intense...
-
809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
11B-809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...
-
809.5.1.2 Activation
All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion...