Raised characters or symbols and Braille designations shall comply with Section 11B-407.4.7.1.2.
Search Results "Elevated Play Component"
-
11B-411.4.7.2 Location
-
11B-411.2.1.4 Additional features
Hall call console additional features, if provided, shall comply with Sections 11B-309 and 11B-411.2.1.4.
-
11B-409.4.4 Leveling
Each car shall automatically stop at a floor landing within a tolerance of ½ inch (12.7 mm) under rated loading to zero loading conditions.
-
11B-407.4.3 Platform to hoistway clearance
The clearance between the car platform sill and the edge of any hoistway landing shall be 1¼ inch (32 mm) maximum.
-
11B-407.4.8.2 Audible indicators
Audible indicators shall comply with Section 11B-407.4.8.2.
-
11B-411.2.1 Hall call consoles
Hall call consoles shall comply with Sections 11B-411.2.1 and 11B-309.
-
11B-407.2.1.1 Height
Call buttons and keypads shall be located within one of the reach ranges specified in Section 11B-308, measured to the centerline of the highest operable part. Exception:...
-
407.4.8.2.1 Signal Type
EXCEPTION: For elevators other than destination-oriented elevators that have a rated speed of 200 feet per minute (1 m/s) or less, a non-verbal audible signal with a frequency of 1500 Hz...
-
407.4.8.2.1 Signal Type
[ECTCR UFAS 4.10.13] EXCEPTION: For elevators other than destination-oriented elevators that have a rated speed of 200 feet per minute (1 m/s) or less, a non-verbal audible signal with...
-
407.4.8.2.1 Signal Type
EXCEPTION: For elevators other than destination-oriented elevators that have a rated speed of 200 feet per minute (1 m/s) or less, a non-verbal audible signal with a frequency of 1500 Hz...
-
11B-409.4.6.1 Size
Control buttons shall be ¾ inch (19.1 mm) minimum in their smallest dimension.
-
409.4.6.1 Size
Control buttons shall be 3/4 inch (19 mm) minimum in their smallest dimension.
-
409.4.6.2 Location
Control panels shall be on a side wall, 12 inches (305 mm) minimum from any adjacent wall.
-
409.4.6.1 Size
Control buttons shall be 3/4 inch (19 mm) minimum in their smallest dimension.
-
409.4.6.1 Size
409.4.6.1 Size. Control buttons shall be 3/4 inch (19 mm) minimum in their smallest dimension.
-
11B-409.4.6.2 Location
Control panels shall be on a side wall, 12 inches (305 mm) minimum from any adjacent wall.
-
11B-409.4.6.1 Size
Control buttons shall be ¾ inch (19.1 mm) minimum in their smallest dimension.
-
11B-409.4.6.1 Size
Control buttons shall be ¾ inch (19.1 mm) minimum in their smallest dimension.
-
11B-409.4.6.2 Location
Control panels shall be on a side wall, 12 inches (305 mm) minimum from any adjacent wall.
-
11B-233.3.1.2.2 Non-elevator buildings
Ground floor residential dwelling units in non-elevator buildings shall be adaptable....
-
Clear Floor or Ground Space: ADA Standard Section 407.2.1.3
Section 407.2.1.3 covers the current ADA Standards for the clear floor or ground space at elevator call controls.
-
4.1.6(3)(c)(iii)
(iii) Equivalent facilitation may be provided with an elevator car of different dimensions when usability can be demonstrated and when all other elements required to be accessible comply...
-
16) Elevator hoistway floor designations and car controls
16) Elevator hoistway floor designations and car controls ADAAG: Must have raised and brailled characters (§§4.10.5; 4.10.12)....
-
11B-407.2.1.3 Clear floor or ground space
The clear floor or ground space required at elevator call buttons must remain free of obstructions including ashtrays, plants, and other decorative elements that prevent wheelchair users...