4. A nominal 32-inch (813 mm) clear opening provided by a standard 6-foot wide (1829 mm) sliding patio door assembly is acceptable.
Search Results "Covered Multifamily Dwelling (FHA)"
-
1132A.3, Item 4
-
1133A.7, Item 3
3. A clear floor space shall not extend into the knee and toe space more than 19 inches (483 mm).
-
11B-809.9.7 Exposed pipes and surfaces
Exposed water supply and drain pipes under sinks and lavatories shall comply with Section 11B-606.5.
-
11B-809.10.7.5 Controls
Controls shall be mounted 44 inches (1118 mm) maximum above the finish floor. The force required to activate controls shall be 5 pounds (22.2 mm) maximum.
-
11B-809.10.8.3 Cabinets
Cabinets shall be removable without the use of specialized knowledge and/or tools. The finished floor shall extend to the wall under the lavatory.
-
11B-809.9.2 Clear width
Kitchens shall have a minimum clear width measured between any cabinet, work surface or the face of any appliance (excluding handles and controls) and the opposing cabinet, work...
-
Covered Entities
Covered Entities Manufacturers of telecommunications equipment and customer premises equipment are required by §255 of the Telecommunications Act of 1966 to "ensure that the equipment...
-
233 Residential Facilities
(1) In sleeping rooms with more than 25 beds covered by this section, a minimum of 5% of the beds shall have clear floor space complying with section 806.2.3 of the 2010 Standards....
-
11B-809.9.1 Clear floor space
Clear floor spaces 30 inches (762 mm) by 48 inches (1219 mm), with centerlines aligned with the centerline of the work surface, appliance, sink or fixture, shall be provided in the...
-
11B-809.10.4 Sufficient maneuvering space
Where doors swing into the toilet and bathing or powder rooms required to comply with Section 11B-809.10, a clear maneuvering space of 30 (762 mm) inches by 48 inches (1219 mm)...
-
11B-809.10.4 Sufficient maneuvering space
Where doors swing into the bathrooms or powder rooms required to comply with Section 11B-809.10, a clear maneuvering space of 30 (762 mm) inches by 48 inches (1219 mm) minimum shall...
-
11B-809.9.1 Clear floor space
Clear floor spaces 30 inches (762 mm) by 48 inches (1219 mm), with centerlines aligned with the centerline of the work surface, appliance, sink or fixture, shall be provided in the...
-
PUBLIC HOUSING
housing may include but is not limited to: the allocation of local, state, or federal financial assistance, Community Development Block Grants, Low Income Housing Tax Credits, the California Multifamily...
-
11B-809.10.8.1 Location
Lavatories without base cabinets shall be installed with the centerline 18 inches (457 mm) minimum from an adjoining wall or fixture to allow for forward approach. Lavatories with...
-
11B-809.10.8.5 Plumbing protection
Plumbing protection shall comply with Section 11B-809.9.7.
-
11B-809.10.5.3 Controls
Controls and operating mechanisms shall comply with Section 11B-309.4. Exception: Shower spray units are not required in bathtubs.
-
11B-809.10.8 Lavatories, vanities, mirrors and towel bars
Bathing rooms or powder rooms required to comply with Section 11B-809.10 shall provide lavatories complying with this section. Where mirrors or towel bars are provided, no less than...
-
11B-809.10.8.4 Knee and toe clearance
Knee and toe clearance shall be provided and comply with Section 11B-306.
-
11B-203.9 Employee workstations
Employee workstations shall be on an accessible route complying with Division 4. Spaces and elements within employee workstations shall only be required to comply with Sections...
-
11B-809.10.7.3 Reinforcement for grab bars
Reinforcement for grabs bars shall comply with the following: Where water closets are not placed adjacent to a side wall capable of accommodating a grab bar, the bathroom...
-
11B-809.10.7.2 Location
Water closets shall be located within bathrooms in a manner that permits a grab bar to be installed on at least one side of the fixture. The centerline of the water closet shall be...
-
11B-809.10.7.4 Seat height
Water closet seats shall be 15 inches (381 mm) minimum and 19 inches (483 mm) maximum measured to the top of the seat above the finish floor.
-
608.4 Seats
EXCEPTION: In residential dwelling units, seats shall not be required in transfer type shower compartments provided that reinforcement has been installed in walls so as to permit the installation...
-
608.4 Seats
EXCEPTION: In residential dwelling units, seats shall not be required in transfer type shower compartments provided that reinforcement has been installed in walls so as to permit the installation...