Section 407.2.1.3 covers the current ADA Standards for the clear floor or ground space at elevator call controls.
Search Results "Push Button"
Commonly Searched Documents
-
Clear Floor or Ground Space: ADA Standard Section 407.2.1.3
-
11B-407.2.1.3 Clear floor or ground space
The clear floor or ground space required at elevator call buttons must remain free of obstructions including ashtrays, plants, and other decorative elements that prevent wheelchair users...
-
Signals: ADA Standard Section 407.2.1.5
Section 407.2.1.5 covers the current ADA Standards for elevator call control signals.
-
11B-407.2.1 Call controls
Where elevator call buttons or keypads are provided, they shall comply with Sections 11B-407.2.1 and 11B-309.4 _|Operation|_. [2010 ADAS] 407.2.1 Call Controls. ...
-
11B-407.2.1 Call controls
Where elevator call buttons or keypads are provided, they shall comply with Sections 11B-407.2.1 and 11B-309.4 _|Operation|_. [2010 ADAS] 407.2.1 Call Controls....
-
11B-407.2.1 Call controls
Where elevator call buttons or keypads are provided, they shall comply with Sections 11B-407.2.1 and 11B-309.4. [2010 ADA Standards] 407.2.1 Call Controls....
-
11B-407.2.1.2 Size and shape
Call buttons shall have square shoulders, be ¾ inch (19.1 mm) minimum in the smallest dimension and shall be raised 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm) above the surrounding...
-
11B-407.2.1.2 Size and shape
Call buttons shall have square shoulders, be ¾ inch (19.1 mm) minimum in the smallest dimension and shall be raised 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm) above the surrounding...
-
11B-407.2.1.2 Size and shape
The buttons shall be activated by a mechanical motion that is detectable. [2010 ADA Standards] 407.2.1.2 Size....
-
408.2.1 Call Buttons
408.2.1 Call Buttons. Elevator call buttons and keypads shall comply with 407.2.1....
-
Location: ADA Standard Section 703.4.2
EXCEPTION: Signs with tactile characters shall be permitted on the push side of doors with closers and without hold-open devices....
-
408.2.1 Call Buttons
Elevator call buttons and keypads shall comply with 407.2.1....
-
408.2.1 Call Buttons
Elevator call buttons and keypads shall comply with 407.2.1....
- Clarity XLC2 Amplified Cordless Phone
-
11B-411.2.1.4.1 Hall call console additional buttons
Hall call console buttons provided in addition to the accessibility function button and keypad buttons shall comply with Section 11B-411.2.1.4.1. ...
-
11B-411.2.1.4.1 Hall call console additional buttons
Hall call console buttons provided in addition to the accessibility function button and keypad buttons shall comply with Section 11B-411.2.1.4.1....
-
11B-411.2.1.4.1 Hall call console additional buttons
Hall call console buttons provided in addition to the accessibility function button and keypad buttons shall comply with Section 11B-411.2.1.4.1....
-
Low Energy Doors and Gates [§404.3]
Low Energy Doors and Gates [§404.3] Low energy doors and gates usually require activation by the user through a push plate or control and are often used in moderate traffic locations...
-
11B-703.4.2 Location
where sign installation locations identified in Section 11B-703.4.2 are obstructed or otherwise unavailable for sign installation, signs with tactile characters shall be permitted on the push...
-
11B-408.2.1 Call buttons
Elevator call buttons and keypads shall comply with Section 11B-407.2.1....
-
11B-408.2.1 Call buttons
Elevator call buttons and keypads shall comply with Section 11B-407.2.1....
-
11B-408.2.1 Call buttons
Elevator call buttons and keypads shall comply with Section 11B-407.2.1....
-
11B-411.2.1.2.5 Audio output
Upon activation of the accessibility function button, the audio output shall provide verbal announcements, including but not limited to, operating instructions, user input confirmation,...
-
407.2.1.2 Size
Call buttons shall be ¾ inch (19 mm) minimum in the smallest dimension. EXCEPTION: Existing elevator call buttons shall not be required to comply with 407.2.1.2....