The audio output shall provide verbal instruction for the user to press the accessibility function button as a response to verbal direction in order to select the destination floor....
Search Results "Food Service Car"
-
11B-411.2.1.7.2 Assignment by touch screen hall call console
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
Height: ADA Standard Section 407.4.6.4.1
Section 407.4.6.4.1 covers the current ADA Standards for the height of the emergency controls in elevator cars.
-
Keypads: ADA Standard Section 407.4.7.2
Section 407.4.7.2 covers the current ADA Standards for designations and indicators on elevator keypads.
-
11B-407.4.6.4.1 Height
Emergency control buttons shall have their centerlines 35 inches (889 mm) minimum above the finish floor.
-
11B-407.4.8.2.3 Frequency
The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
11B-407.4.7.2 Keypads
Keypads shall be identified by characters complying with Section 11B-703.5 and shall be centered on the corresponding keypad button. The number five key shall have a single raised...
-
11B-407.4.7.2 Keypads
Keypads shall be identified by characters complying with Section 11B-703.5 and shall be centered on the corresponding keypad button. The number five key shall have a single raised...
-
Height: ADA Standard Section 407.3.3.1
Section 407.3.3.1 covers the current ADA Standards for the height requirements of an elevators reopening device.
-
Duration: ADA Standard Section 407.3.3.3
Section 407.3.3.3 covers the current ADA Standards for the duration of an elevators reopening device.
-
Contact: ADA Standard Section 407.3.3.2
Section 407.3.3.2 covers the current ADA Standards for the contact requirements of an elevators reopening device.
-
11B-407.4.8.2.3 Frequency
The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
11B-407.4.6.4.1 Height
Emergency control buttons shall have their centerlines 35 inches (889 mm) minimum above the finish floor.
-
11B-411.2.1.7.2 Assignment by touch screen hall call console
The audio output shall provide verbal instruction for the user to press the accessibility function button as a response to verbal direction in order to select the destination floor....
-
Section 36.302(c) Service Animals (Section-by-Section Analysis)
to permit the use of service animals by an individual with a disability.''...
-
What about a service animal that is not accompanying a qualified individual with a disability?
When a service animal is not accompanying a passenger with a disability, the airline's general policies on the carriage of animals usually apply....
-
Sinks: ADA Standard Section 212.3
Section 212.3 covers scoping requirements in the current ADA Standards for sinks.
-
4.10.12(4)
Controls shall be located on a front wall if cars have center opening doors, and at the side wall or at the front wall next to the door if cars have side opening doors (see Fig. 23(c) and...
-
4.10.12(4)
Controls shall be located on a front wall if cars have center opening doors, and at the side wall or at the front wall next to the door if cars have side opening doors (see Fig. 23(c) and...
-
ยง 37.107 Acquisition of passenger rail cars by private entities primarily engaged in the business of transporting people
[See subsections ...]
-
Q25. When can service animals be excluded?
When can service animals be excluded? A....