(6) The appliance shall be placed 80 in (2030 mm) above the highest floor level within the space or 6 in (152 mm) below the ceiling, whichever is lower.
Search Results "Fire Alarm System"
-
4.28.3(6)
-
4.28.3(7)
(7) In general, no place in any room or space required to have a visual signal appliance shall be more than 50 ft (15 m) from the signal (in the horizontal plane). In large rooms and...
-
4.28.3(8)
(8) No place in common corridors or hallways in which visual alarm signalling appliances are required shall be more than 50 ft (15 m) from the signal....
-
4.28.4* AUXILIARY ALARMS
Accessible sleeping accommodations shall have a visual alarm connected to the building emergency alarm system or shall have a standard 110-volt electrical receptacle into which such an alarm...
-
4.28.4* Auxiliary Alarms
Units and sleeping accommodations shall have a visual alarm connected to the building emergency alarm system or shall have a standard 110-volt electrical receptacle into which such an alarm...
-
Scoping [4.1.3(14)]
Scoping [4.1.3(14)] ADAAG requires both audible and visual alarms in facilities that have emergency warning systems whether building-wide systems or self-contained units are provided....
-
Medical Care Facilities
Medical Care Facilities Requirements for alarms may be modified in medical care settings according to standard industry practice....
-
Visual Alarms [4.28.3]
Visual Alarms [4.28.3] In general, it is not sufficient to install visual signals only at audible alarm locations....
-
Mounting Height
Mounting Height ADAAG specifies a signal height 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. (This can be measured...
-
Location and Spacing
Provisions for the spacing of visual alarms in hallways and corridors generally require one fixture every 100 feet....
-
Auxiliary Alarms [4.28.4]
connected to the building alarm system or have an outlet for a portable device....
-
CHAPTER 9 FIRE PROTECTION SYSTEMS
ETA Editor's Note Sections from California Building Code Chapter 9 not adopted by Division of the State Architect - Access Compliance (DSA-AC) omitted. To see the entire...
-
CHAPTER 9 FIRE PROTECTION SYSTEMS
ETA Editor's Note Sections from California Building Code Chapter 9 that are not adopted by Division of the State Architect - Access Compliance (DSA-AC) have been omitted. To...
-
OCCUPANT NOTIFICATION SYSTEMS
People with cognitive disabilities can hear standard alarms and voice announcements and see visual indicators that warn of danger and the need to evacuate....
-
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
-
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
-
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
-
[F] 907.5 Occupant notification systems
...
-
[F] 907.5.2.3.2 Groups R-1 and R-2.1
Group R-1 and R-2.1 dwelling units or sleeping units in accordance with Table 907.5.2.3.2 shall be provided with a visible alarm notification appliance, activated by both the in-room smoke...
-
907.5.2.3.3 Group R-2
In Group R-2 occupancies required by Section 907 to have a fire alarm system, all dwelling units and sleeping units shall be provided with the capability to support visible alarm notification...
-
907.5.2.3.4 Groups R-2.1, R-3.1 and R-4
who are hearing impaired, shall be provided with notification appliances for the hearing impaired installed in accordance with NFPA 72 and which shall activated upon initiation of the fire...
-
907.5.2.3.2 Groups R-1 and R-2.1
Habitable spaces in dwelling units and sleeping units in Group R-1 and R-2.1 occupancies in accordance with Table 907.5.2.3.2 shall be provided with visible alarm notification....
-
[F] 907.5.2.3.2 Groups R-1 and R-2.1
Habitable spaces in dwelling units and sleeping units in Group R-1 and R-2.1 occupancies in accordance with Table 907.5.2.3.2 shall be provided with visible alarm notification....
-
[F] 907.5.2.3.3 Group R-2
In Group R-2 occupancies required by Section 907 to have a fire alarm system, each story that contains dwelling units and sleeping units shall be provided with the capability to support...