407.3.3.2 Contact
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.4.8.2.3 Frequency
The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish floor.
-
407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
407.4.8.2.3 Frequency
The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
407.3.3.3 Duration
407.3.3.3 Duration. Door reopening devices shall remain effective for 20 seconds minimum.
-
407.4.8.2.3 Frequency
407.4.8.2.3 Frequency. The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
407.3.3.2 Contact
407.3.3.2 Contact. The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
407.3.3.1 Height
407.3.3.1 Height. The device shall be activated by sensing an obstruction passing through the opening at 5 inches (125 mm) nominal and 29 inches (735 mm) nominal above the finish...
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.4.8.2.3 Frequency
The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
11B-407.3.3.3 Duration
Door reopening devices shall remain effective for 20 seconds minimum.
-
11B-407.3.3.2 Contact
The device shall not require physical contact to be activated, although contact is permitted to occur before the door reverses.
-
11B-407.4.8.2.3 Frequency
The verbal annunciator shall have a frequency of 300 Hz minimum to 3000 Hz maximum.
-
11B-407.3.3.1 Height
The device shall be activated by sensing an obstruction passing through the opening at 5 inches (127 mm) nominal and 29 inches (737 mm) nominal above the finish floor.
-
Elevator Landing Requirements [§407.2]
Elevator Landing Requirements [§407.2]...
-
408.4.1 Car Dimensions and Doors
Elevator cars shall provide a clear width 42 inches (1065 mm) minimum and a clear depth 54 inches (1370 mm) minimum....