409.4.7.4 Cord. The telephone cord shall be 29 inches (735 mm) long minimum.
Search Results "Private Residence Elevator"
-
409.4.7.4 Cord
-
Elevators: ADA Standard Section 206.6
Section 206.6 covers scoping requirements in the most current ADA Standards for accessible routes to elevators.
-
409 Private Residence Elevators
-
409.1 General
Private residence elevators that are provided within a residential dwelling unit required to provide mobility features complying with 809.2 through 809.4 shall comply with 409 and with ASME...
-
409.2 Call Buttons
Call buttons shall be ¾ inch (19 mm) minimum in the smallest dimension and shall comply with 309.
-
409.3 Elevator Doors
Hoistway doors, car doors, and car gates shall comply with 409.3 and 404. EXCEPTION: Doors shall not be required to comply with the maneuvering clearance requirements in 404.2.4.1...
-
409.3.1 Power Operation
Elevator car and hoistway doors and gates shall be power operated and shall comply with ANSI/BHMA A156.19 (1997 or 2002 edition) (incorporated by reference, see "Referenced Standards" in...
-
409.3.2 Location
Elevator car doors or gates shall be positioned at the narrow end of the clear floor spaces required by 409.4.1....
-
409.4 Elevator Cars
Private residence elevator cars shall comply with 409.4....
-
409.4.1 Inside Dimensions of Elevator Cars
Elevator cars shall provide a clear floor space of 36 inches (915 mm) minimum by 48 inches (1220 mm) minimum and shall comply with 305....
-
409.4.2 Floor Surfaces
Floor surfaces in elevator cars shall comply with 302 and 303....
-
409.4.3 Platform to Hoistway Clearance
The clearance between the car platform and the edge of any landing sill shall be 1-½ inch (38 mm) maximum.
-
409.4.4 Leveling
Each car shall automatically stop at a floor landing within a tolerance of ½ inch (13 mm) under rated loading to zero loading conditions.
-
409.4.5 Illumination Levels
Elevator car illumination shall comply with 407.4.5....
-
409.4.6 Car Controls
Elevator car control buttons shall comply with 409.4.6, 309.3, 309.4, and shall be raised or flush....
-
409.4.6.1 Size
Control buttons shall be 3/4 inch (19 mm) minimum in their smallest dimension.
-
409.4.6.2 Location
Figure 409.4.6.2 Location of Private Residence Elevator Control Panel...
-
409.4.7 Emergency Communications
Emergency two-way communication systems shall comply with 409.4.7.
-
409.4.7.1 Type
A telephone and emergency signal device shall be provided in the car.
-
409.4.7.2
The telephone and emergency signaling device shall comply with 309.3 and 309.4.
-
409.4.7.3 Compartment
If the telephone or device is in a closed compartment, the compartment door hardware shall comply with 309.
-
409.4.7.4 Cord
The telephone cord shall be 29 inches (735 mm) long minimum.
-
Private Residence Elevators: ADA Standard Section 409
Section 409 covers the current ADA Standards for private residence elevators....
-
General: ADA Standard Section 409.1
Section 409.1 of the ADA Standards covers information in the current ADA Standards for private residence elevators....