Examples of such diagnostic equipment include examination tables and chairs, weight scales, mammography equipment, and other imaging equipment....
Search Results "Mammography"
-
A. Final Regulatory Assessment (EO 13563 and EO 12866)
-
3. Getting Access to Medical Equipment
following: 69% had difficulty using exam tables; 60% had difficulty being weighed due to inaccessible scales; 45% had difficulty using x-ray equipment, such as mammography...
-
M303 Diagnostic Equipment Used by Patients Seated in a Wheelchair
-
M303 Diagnostic Equipment Used by Patients Seated in a Wheelchair
-
M303.1 General
Diagnostic equipment used by patients seated in a wheelchair shall comply with M303.
-
M303.1 General
Diagnostic equipment used by patients seated in a wheelchair shall comply with M303.
-
M303.2 Wheelchair Spaces
A wheelchair space complying with M303.2 shall be provided at diagnostic equipment. Advisory M303.2 Wheelchair Spaces. A wheelchair space can be used to accommodate patients who...
-
M303.2 Wheelchair Spaces
Wheelchair spaces complying with M303.2 shall be provided at diagnostic equipment.
-
M303.2.1 Orientation
Wheelchair spaces shall be designed so that a patient seated in a wheelchair orients in the same direction that a patient not seated in a wheelchair orients when the diagnostic...
-
M303.2.1 Orientation
Wheelchair spaces shall be designed so that a patient seated in a wheelchair orients in the same direction that a patient not seated in a wheelchair orients when the diagnostic...
-
M303.2.2 Width
Wheelchair spaces shall be 36 inches (915 mm) wide minimum.
-
M303.2.2 Width
Wheelchair spaces shall be 36 inches (915 mm) wide minimum. EXCEPTION: Wheelchair spaces located on raised platforms shall be permitted to be 32 inches (815 mm) wide minimum to a...
-
M303.2.3 Depth
The depth of wheelchair spaces shall comply with M303.2.3.
-
M303.2.3 Depth
Where wheelchair spaces can be entered from the front or rear, the wheelchair space shall be 48 inches (1220 mm) deep minimum. Where wheelchair spaces can be entered only from the...
-
M303.2.4 Equipment Clearances
Where wheelchair spaces are entered from the rear and includes space beneath components, wheelchair spaces shall include knee and toe clearances complying with M303.2.4.1 for breast...
-
M303.2.4.1 Breast Platforms
Wheelchair spaces beneath breast platforms shall comply with M303.2.4.1.
-
M303.2.4.1.1 Depth
Wheelchair spaces shall include knee and toe clearance 25 inches (635 mm) deep minimum and 28 inches (710 mm) deep maximum.
-
M303.2.4.1.2 Height
Wheelchair spaces shall include toe clearance 9 inches (230 mm) high minimum above the floor measured to a depth of 6 inches (150 mm) maximum from the toe end of the wheelchair...
-
M303.2.5 Surfaces
Wheelchair space surfaces shall not slope more than 1:48 in any direction.
-
M303.2.4 Knee and Toe Clearance
Wheelchair spaces shall include knee and toe clearance complying with M303.2.4. The depth of the wheelchair space shall include knee and toe clearance of 17 inches (430 mm) minimum...
-
M303.2.4.1 Toe Clearance
Toe clearance shall be provided at a height of 9 inches (230 mm) above the floor to a depth of 6 inches (150 mm) maximum.
-
M303.2.4.2 Knee Clearance
Knee clearance shall be provided at a depth of 11 inches (280 mm) minimum and 25 inches (635 mm) maximum at 9 inches (230 mm) above the floor and at a depth of 8 inches (205 mm)...
-
M303.2.5 Surfaces
Wheelchair space surfaces shall not slope more than 1:48 in any direction.
-
M303.4.1 Breast Platforms
The height of the breast platform shall be 30 inches (760 mm) high minimum and 42 inches (1065 mm) high maximum above the floor when in use by a patient seated in a wheelchair.