The International Symbol of TTY shall comply with Figure 703.7.2.2.
Search Results "Program Relocation to Accessible Facility"
Commonly Searched Documents
-
703.7.2.2 International Symbol of TTY
-
2.8 Openings
Openings in the surface of ORARs shall be small enough to prevent passage of a 1/2 inch (13 mm) diameter sphere. Where possible, elongated openings should be placed...
-
6.8 Resting Intervals
Resting intervals shall comply with 6.8.
-
6.8.1 Size
The resting interval length shall be a minimum of 60 inches (1525 mm) long by 60 inches (1525 mm) wide.
-
1018.8 Resting Intervals
This section contains the technical requirements for the size (1018.8.1) and slope (1017.8.2) of resting intervals.
-
1018.8.1 Size
This section requires resting intervals to be 60 inches minimum by 60 inches minimum.
-
1018.8.1 Size
Resting intervals shall be 60 inches minimum (1525 mm) by 60 inches (1525 mm) minimum.
-
1018.8 Resting Intervals
Resting intervals shall comply with 1018.8.
-
1014.2.2.2 Turning Space
A turning space complying with 304.3 shall be provided within the camp shelter.
-
11B-604.8.1.3 Approach
11B-604.8.1.3 Approach. Compartments shall be arranged for left-hand or right-hand approach to the water closet.
-
11B-604.8.2.3 Grab bars
11B-604.8.2.3 Grab bars. Grab bars shall comply with Section 11B-609. A side-wall grab bar complying with Section 11B-604.5.1 shall be provided on both sides of the compartment.
-
11B-703.7.2.2 International Symbol of TTY
11B-703.7.2.2 International Symbol of TTY. The International Symbol of TTY shall comply with Figure 11B-703.7.2.2.
-
11B-703.7.2.3 Volume control telephones
11B-703.7.2.3 Volume control telephones. Telephones with a volume control shall be identified by a pictogram of a telephone handset with radiating sound waves on a square field such...
-
11B-604.8.2.3 Grab bars
Grab bars shall comply with Section 11B-609. A side-wall grab bar complying with Section 11B-604.5.1 shall be provided on both sides of the compartment.
-
1009.4.1 Standby power
The elevator shall meet the emergency operation and signaling device requirements of California Code of Regulations, Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety...
-
11B-604.8.1.3 Approach
Compartments shall be arranged for left-hand or right-hand approach to the water closet.
-
11B-703.7.2.3 Volume control telephones
Telephones with a volume control shall be identified by a pictogram of a telephone handset with radiating sound waves on a square field such as shown in Figure 11B-703.7.2.3.
-
11B-703.7.2.2 International Symbol of TTY
The International Symbol of TTY shall comply with Figure 11B-703.7.2.2.
-
11B-703.7.1 Finish and contrast
Symbols of accessibility and their background shall have a non-glare finish....
-
703.7.1 Finish and Contrast
Symbols of accessibility and their background shall have a non-glare finish....
-
703.7.1 Finish and Contrast
Symbols of accessibility and their background shall have a non-glare finish....
-
II-7.3200 911 lines
Where a 911 telephone line is available, a separate seven-digit telephone line must not be substituted as the sole means for nonvoice users to access 911 services....
-
11B-703.7.1 Finish and contrast
Symbols of accessibility and their background shall have a non-glare finish....
-
11B-406.5.1 Location
Curb ramps and the flared sides of curb ramps shall be located so that they do not project into vehicular traffic lanes, parking spaces, or parking access aisles....