(8) No place in common corridors or hallways in which visual alarm signalling appliances are required shall be more than 50 ft (15 m) from the signal.
Search Results "NFPA: National Fire Protection Association"
Commonly Searched Documents
-
4.28.3(8)
-
Visual Alarms [4.28.3]
Visual Alarms [4.28.3] In general, it is not sufficient to install visual signals only at audible alarm locations. Audible alarms installed in corridors and lobbies can be heard...
-
A4.28.3 Visual Alarms
The specifications in this section do not preclude the use of zoned or coded alarm systems.
-
4.28.3* Visual Alarms
Visual alarm signal appliances shall be integrated into the building or facility alarm system. If single station audible alarms are provided then single station visual alarm signals...
-
4.28.3(6)
(6) The appliance shall be placed 80 in (2030 mm) above the highest floor level within the space or 6 in (152 mm) below the ceiling, whichever is lower.
-
4.28.1 General
Alarm systems required to be accessible by 4.1 shall comply with 4.28. At a minimum, visual signal appliances shall be provided in buildings and facilities in each of the following...
-
4.28.1 GENERAL
Alarm systems required to be accessible by 4.1 shall comply with 4.28.
-
A4.28.3 VISUAL ALARMS
The specifications in this section do not preclude the use of zoned or coded alarm systems. In zoned systems, the emergency exit lights in an area will flash whenever an audible...
-
§ 38.159(c)(4) Ramp barriers
(4) Ramp barriers. Each side of the ramp shall have barriers at least 2 inches (50 mm) high to prevent mobility aid wheels from slipping off.
-
§ 38.83(c)(4) Ramp barriers
(4) Ramp barriers. Each side of the ramp or bridge plate shall have barriers at least 2 inches high to prevent mobility aid wheels from slipping off.
-
907.5.2.3.5 Groups R-2.1, R-3.1 and R-4
Protective social care facilities which house persons who are hearing impaired, shall be provided with notification appliances for the hearing impaired installed in accordance with NFPA...
-
809.5.1.1 Alarm Appliances
Where alarm appliances are provided within a residential dwelling unit as part of the building fire alarm system, they shall comply with 702....
-
809.5.1.1 Alarm Appliances
Where alarm appliances are provided within a residential dwelling unit as part of the building fire alarm system, they shall comply with 702....
-
809.5.1.1 Alarm Appliances
Where alarm appliances are provided within a residential dwelling unit as part of the building fire alarm system, they shall comply with 702....
-
E102.2 ANSI/HFES (Section-by-Section Analysis)
It covers issues associated with designing accessible software for people with a wide range of physical, sensory and cognitive abilities, including those who are temporarily disabled and...
-
Visible Alarms in Alterations to Existing Facilities
Section 215.1 of the 2010 Standards adds a new exception to the scoping requirement for visible alarms in existing facilities so that visible alarms must be installed only when an existing fire...
-
ANSI/AAMI HE 75
As discussed in the relevant sections below, the Access Board considered the recommended practices regarding accessibility in Chapter 16 of ANSI/AAMI HE 75 in developing the...
-
§ 37.3 Intercity rail transportation
Intercity rail transportation means transportation provided by Amtrak.
-
OCCUPANT NOTIFICATION SYSTEMS
People who are blind or have low vision can hear standard building fire alarms and voice announcements over public address systems that warn of a danger or the need to evacuate or that provide...
-
F215.1 General
Where fire alarm systems provide audible alarm coverage, alarms shall comply with F215....
-
215.1 General
Where fire alarm systems provide audible alarm coverage, alarms shall comply with 215....
-
215.1 General
Where fire alarm systems provide audible alarm coverage, alarms shall comply with 215....
-
4.2.1 General
Where fire rings, grills, fireplaces, or woodstoves are provided, each shall comply with section 4.2. Exception....