Search Results "Signage"
-
T702 Signs
-
T702.2 Character Style
Characters shall be displayed in sans serif fonts and shall not use italic, oblique, script, highly decorative, or other unusual forms.
-
T702.3 Character Proportions
Characters shall use fonts where the width of the uppercase letter “O” is 55 percent minimum and 110 percent maximum of the height of the uppercase letter “I”.
-
T702.4 Character Height
Character height shall comply with Table T702.4. Character height shall be based on the uppercase letter “I”. Table T702.4—Character Height Sign...
-
T702.5 Stroke Thickness
Stroke thickness of the uppercase letter “I” shall be 10 percent minimum and 30 percent maximum of the height of the character.
-
502.6 Identification
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the...
-
T702.6 Character Spacing
Character spacing shall be measured between the two closest points of adjacent characters, excluding word spaces. Spacing between individual characters shall be 10 percent minimum...
-
T702.7 Line Spacing
Spacing between the baselines of separate lines of characters within a message shall be 135 percent minimum and 170 percent maximum of the character height.
-
T702.8 Contrast
Characters shall contrast with their background with either light characters on a dark background or dark characters on a light background. Where provided, protective surfaces over...
-
1009.9 Signage
Signage indicating special accessibility provisions shall be provided as shown: Each door providing access to an area of refuge from an adjacent floor area shall be identified by a...
-
1009.9 Signage
Signage indicating special accessibility provisions shall be provided as shown: Each door providing access to an area of refuge from an adjacent floor area shall be identified by a...
-
1009.10 Directional signage
Directional signage complying with Chapter 11B, Section 11B-703.5 indicating the location of the other means of egress and which of those are accessible means of egress shall be provided...
-
1009.10 Directional signage
Directional signage complying with Chapter 11B, Section 11B-703.5 indicating the location of the other means of egress and which of those are accessible means of egress shall be provided...
-
703 Signs
-
T703 International Symbol of Accessibility
-
703.1 General
Signs shall comply with 703. Where both visual and tactile characters are required, either one sign with both visual and tactile characters, or two separate signs, one with visual,...
-
1010.1.9.8.1 Delayed egress locking system
The delayed egress locking system shall be installed and operated in accordance with all of the following: … 4. An attempt to egress shall initiate an irreversible process that...
-
1010.2.13.1 Delayed egress locking system
The delayed egress locking system shall be installed and operated in accordance with all of the following: … 4. An attempt to egress shall initiate an irreversible process that...
-
703.2 Raised Characters
Raised characters shall comply with 703.2 and shall be duplicated in braille complying with 703.3. Raised characters shall be installed in accordance with 703.4. Advisory 703.2...
-
703.2.1 Depth
Raised characters shall be 1/32 inch (0.8 mm) minimum above their background.
-
703.2.2 Case
Characters shall be uppercase.
-
3) Signs
3) Signs ADAAG: * Signs designating permanent rooms and spaces (men's and women's rooms; room numbers; exit signs) must have raised and Brailled letters; must comply with...
-
703.2.3 Style
Characters shall be sans serif. Characters shall not be italic, oblique, script, highly decorative, or of other unusual forms.
-
703.2.4 Character Proportions
Characters shall be selected from fonts where the width of the uppercase letter "O" is 55 percent minimum and 110 percent maximum of the height of the uppercase letter "I".