This document, portion of document or clip from legal proceedings may not represent all of the facts, documents, opinions, judgments or other information that is pertinent to this case. The entire case, including all court records, expert reports, etc. should be reviewed together and a qualified attorney consulted before any interpretation is made about how to apply this information to any specific circumstances.

Spy City Café:

e. The force required to push or pull open the interior hinged vestibule doors to the men's and women's toilet rooms designated as accessible is 10 pounds of force (lbf), which exceeds the maximum allowable door opening force of 5 lbf. See Standards § 4.13.11(2)(b).

f. The bottom edges of the reflecting surfaces of the mirrors in the men's and women's toilet rooms located outside the Café and designated as accessible are mounted 57 ½" [sic] from the finished floor, which exceeds the maximum allowable height of 40" above the finished floor. See Standards § 4.19.6.

g The height of the main cashier counter is 42" above the finished floor, exceeding the maximum allowable height of 36". See Standards § 7.2(1).

h. The Café has no accessible seating. Where fixed tables are provided at least 5% but not less than one of the fixed tables shall be accessible. See Standards § 5.1.