United States of America v. The International Spy Museum - Settlement Agreement
Restrooms Main Lobby:
k. The restroom vestibule door does not have the required minimum of 18" maneuvering clearance on the latch side of the door. See Standards § 4.13.6.
l. The force required to push or pull open the interior hinged doors to the restroom vestibule door is 10 lbf, which exceeds the maximum allowable door opening force of 5 lbf. See Standards § 4.13.11(2)(b).
m. The handles, locks, and other operating devices of the men's and women's toilet stall doors do not have a shape that is easy to grasp with one hand and require tight grasping and twisting actions of the wrist to operate. See Standards § 4.13.9.
n. The force required to push or pull open the interior hinged doors to the women's toilet room door is 13 lbf, which exceeds the maximum allowable door opening force of 5 lbf. See Standards § 4.13.11(2)(b).
o. The operation of the feminine product dispenser in the women's toilet room requires tight grasping and twisting of the wrist. See Standards § 4.27.4.