11B-206.2.7 Press boxes.

Press boxes in assembly areas shall be on an accessible route.

Exceptions:

1. An accessible route shall not be required to press boxes in bleachers that have points of entry at only one level provided that the aggregate area of all press boxes is 500 square feet (46 m2) maximum.

2. An accessible route shall not be required to free-standing press boxes that are elevated above grade 12 feet (3660 mm) minimum provided that the aggregate area of all press boxes is 500 square feet (46 m2) maximum.

[2010 ADAS] Advisory 206.2.7 Press Boxes Exception 2.  Where a facility contains multiple assembly areas, the aggregate area of the press boxes in each assembly area is to be calculated separately. For example, if a university has a soccer stadium with three press boxes elevated 12 feet (3660 mm) or more above grade and each press box is 150 square feet (14 m2), then the aggregate area of the soccer stadium press boxes is less than 500 square feet (46 m2) and Exception 2 applies to the soccer stadium. If that same university also has a football stadium with two press boxes elevated 12 feet (3660 mm) or more above grade and one press box is 250 square feet (23 m2), and the second is 275 square feet (26 m2), then the aggregate area of the football stadium press boxes is more than 500 square feet (46 m2) and Exception 2 does not apply to the football stadium.  