When a portable patient lift or stretcher is to be used, additional clear floor space will be needed to maneuver the lift or stretcher....
Search Results "Patient Lift"
-
Clear Floor and Turning Space Inside Examination Rooms
-
M302.4 Lift Compatibility
Diagnostic equipment shall be usable with portable patient lifts and, when in use with such lifts, shall comply with M302.4.1 or M302.4.2. ...
-
M302.4 Lift Compatibility
Diagnostic equipment shall be usable with a patient lift and shall comply with M302.4.1 or M302.4.2....
-
M302.4.1 Clearance in Base
The base of the equipment shall provide a clearance 44 inches (1120 mm) wide minimum, 6 inches (150 mm) high minimum measured from the floor, and 36 inches (915 mm) deep minimum...
-
M302.4.1 Clearance in Base
The base of the diagnostic equipment shall provide a clearance 39 inches (990 mm) wide minimum, 6 inches (150 mm) high minimum measured from the floor, and 36 inches (915 mm) deep...
-
M302.4.2 Clearance Around Base
The base of the equipment shall provide a clearance 6 inches (150 mm) high minimum measured from the floor and 36 inches (915 mm) deep minimum measured from the edge of the...
-
M302.4.2 Clearance Around Base
The base of the diagnostic equipment shall provide a clearance 6 inches (150 mm) high minimum measured from the floor and 36 inches (915 mm) deep minimum measured from the edge of...
-
Accessible Medical Equipment
We provide participants transfer assistance on and off of equipment (this includes use of lift equipment when needed). ...
-
4. Getting What You Need During Your Visit
If you will need it, ask if they have transfer or lifting equipment and/or a lift team....
-
Exam Tables and Chairs
Transfers may also require use of equipment, such as a transfer board or patient lift....
-
Using Patient Lifts
Using Patient Lifts Medical providers may need a lift in order to transfer some patients safely onto an exam table....
-
Portable Floor Lifts
The provider should ensure that it does not schedule for the same appointment time more than one patient needing the lift....
-
Overhead Track Lifts
Overhead Track Lifts Overhead track lifts include ceiling mounted lifts and lifts mounted on a frame supported from the floor....
-
Ceiling Mounted Lifts
Ceiling Mounted Lifts Ceiling mounted lifts are permanently mounted to the ceiling structure and run along one or more tracks....
-
Free-Standing Overhead Lifts
Free-Standing Overhead Lifts Another type of overhead lift is supported from a frame that rests on the floor....
-
Additional Transfer Techniques: Use of Stretchers and Gurneys
This approach involves a two step process in which the patient must transfer from their wheelchair to the stretcher, usually in a different space or area away from the equipment, and then...
-
EXHIBIT 1 JEFFERSON OUTPATIENT IMAGING ADA POLICY AND PROCEDURE
When a patient with a mobility impairment or other disability seeks assistance with transferring to imaging equipment or examination tables, Jefferson Outpatient will safely assist the patient...
-
Lift Compatibility (M301.4 and M302.4)
with a patient lift for patients with disabilities for whom independent transfer may not be possible....
-
Clearance in Base (M301.4.1 and M302.4.1)
Clearance in the base of the equipment allows the legs of a portable floor lift to fit under the base of the equipment....
-
Clearance Around Base (M301.4.2 and M302.4.2)
Clearance around the base of the equipment allows the legs of a portable floor lift to straddle the base....
-
Overhead Lifts
equipment does not affect the operation of overhead lifts....
-
5.7 Lift Compatibility Recommendations
5.7 Lift Compatibility Recommendations...
-
5.7.1 Lift Compatibility Clearance in Base for M301
5.7.1 Lift Compatibility Clearance in Base for M301 Description: For portable floor lifts to be effective, they must deploy at diagnostic equipment such that the boom of the lifts can...
-
5.7.1.1 Lift Compatibility Clearance in Base for Stretchers (M301)
IEC 60601-2-52 provides requirements for stretchers and includes a lift clearance at the 39 inch width....